![ABB FSO-12 User Manual Download Page 68](http://html.mh-extra.com/html/abb/fso-12/fso-12_user-manual_2726068.webp)
68 Safety functions
With ramp monitoring (SS1-r)
The operation of the SS1-r function with speed limit activated SBC is described in the
time diagram and table below. For configuration, see section
with speed limit activated SBC
on page
A
SBC speed (parameter
): Speed limit below which the FSO activates the SBC
(brake) and drive STO functions while ramping.
B
SBC time to zero
(parameter
): Time from the SBC activation to the moment
when the safety function is completed and the SS1 completed indication (parameter
) goes on. The acknowledgment becomes allowed. You must set this to the
estimated time in which the motor brakes to a stop from the maximum speed.
C
Response time (depends on system configuration, see page
Ramp monitoring limits
Drive STO state
& indication
SS1 request
Motor speed
Time
SS1 state &
indication
1
6
2
5
SBC output
3
A
C
SS1 completed
indication
SAR1
monitoring
3b
B
4