Safety functions 131
SMS function, version 2
The operation of the SMS function, version 2 is described in the time diagram and
table below. For configuration, see section
How to configure SMS, version 2
on
page
The drive limits the motor speed so that it stays between the SMS limit positive and
negative. If the motor speed stills hits the SMS trip limit positive or negative, the FSO
module activates the SSE function (see section
on
page
for more information on how to configure the SSE function).
Note
: If you use the SMS function, version 2 and you have to remove the FSO
module from the drive, do these steps:
1. Re-configure the FSO module so that the SMS function, version 2 is deactivated
Disabled
). For more
.
2. Remove the FSO module from the drive.
This removes the SMS limits from the drive. Unnecessary limits can affect the normal
operation of the drive.
A
SMS trip limit positive (parameter
B
SMS trip limit negative (parameter
)
C
SMS limit positive (parameter
D
SMS limit negative (parameter
)
SMS trip limits (A and B)
B
A
C
D
Motor speed
Time
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...