372 Technical data
Control connection data
Terminal and cable entry data for the control cables
Logic levels
“0” < 5 V, “1” > 15 V
Digital input impedance
4 kohm
Digital output capability
150 mA @ 20 V each, 700 mA @ 20 V total when all outputs are
in use
Max. cable length
between digital
input/output and external
device
250 m (820 ft)
Max. current through
signal ground terminals
(X113:5, X113:5, X114:5,
X114:6)
1000 mA
Conductor size
Tightening
torque
Solid or stranded
Stranded, ferrule
without plastic sleeve
Stranded, ferrule with
plastic sleeve
Min/Max
Min/Max
Min/Max
Min/Max
Min/Max
Min/Max
mm
2
AWG
mm
2
AWG
mm
2
AWG
N·m
lbf·in
0.14/1.5
26/16
0.25/1.5
23/16
0.25/0.5
23/21
0.24
2.1
Conductor size, two conductors with the same cross section
Tightening
torque
Solid
Stranded
Stranded, ferrules
without plastic
sleeve
Stranded, TWIN
ferrules with
plastic sleeve
Min/Max Min/Max Min/Max Min/Max Min/Max Min/Max Min/Max Min/Max
mm
2
AWG
mm
2
AWG
mm
2
AWG
mm
2
AWG
N·m lbf·in
0.08/0.5
28/21
0.08/0.75
28/19
0.25/0.34
23/22
0.5/0.5
21/21
0.24
2.1
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...