356 Fault tracing
AAA6 FSO SLS3 hit
FSO module detected an
SLS3 speed limit
violation.
Make sure that SLS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
).
2)
AAA7 FSO SLS4 hit
FSO module detected an
SLS4 speed limit
violation.
Make sure that SLS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
.
2)
AAA8 FSO SMS hit
FSO module detected an
SMS speed limit violation.
Make sure that SMS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
).
2)
AAA9 FSO SAR0 hit
FSO module detected an
SAR0 limit violation.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
AAAA FSO SAR1 hit
FSO module detected an
SAR1 limit violation.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
AAB2 FSO ramp time hit FSO module detected a
violation of a time
monitored ramp.
Make sure that the drive can
decelerate the load within the time
defined for ramp time monitoring.
• Check the drive ramp time settings.
• Check that the drive can in fact
accomplish the deceleration along
the ramp defined.
Make sure that the limit for ramp time
monitoring of the FSO module
exceeds the actual drive ramp time.
The parameter varies depending on
the safety function. For the SS1
function it is
2)
AAB3 FSO zero spd hit
Drive speed rushed
during zero speed delay
(
or
).
Check the drive.
2)
Code
(hex)
Name
Cause
What to do
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...