304 Parameters
SS1.21 SS1 output
Sets the digital output that indicates the
activity of the SS1 function. Active from the
SS1 request until the function has been
acknowledged.
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7
Single output X113:7
DO X113:8
Single output X113:8
DO X113:9
Single output X113:9
DO X114:7
Single output X114:7
DO X114:8
Single output X114:8
DO X114:9
Single output X114:9
SS1.22 SS1 completed
output
Sets the digital output that indicates the
completion of the SS1 function. See the
diagrams in section
on
page
.
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7
Single output X113:7
DO X113:8
Single output X113:8
DO X113:9
Single output X113:9
DO X114:7
Single output X114:7
DO X114:8
Single output X114:8
DO X114:9
Single output X114:9
41
SLSx
Parameters for the SLS1
…
4 functions
SLSx.02 SLS
acknowledgement
Sets the acknowledgement method used in
the SLS1
…
4 functions.
Manual
The FSO module reads the external SLS
acknowledgement signal through the digital
input defined by parameter
. The FSO
module accepts the acknowledgement after
the SLS request has been removed and the
SLS limit has been achieved (that is, SLS
monitoring is on).
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...