Configuration 237
Configuring SS1
To configure the SS1 function, set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter group
on
page
For more information on the SS1 function, see page
How to configure SS1 with time monitoring (SS1-t)
Example:
The figure below shows an example of an SS1-t set-up:
• SS1 function activated (
=
Version 1
)
• SAR1 emergency ramp (always with the SS1 function)
• SS1 with time monitored ramp (
=
SS1-t
)
• security delay for activating the drive STO: 2000 ms
2000 ms
)
• automatic acknowledgement (
Automatic
)
• redundant emergency stop button connected to input
DI X113:1 & X114:1
)
• single output connected (
=
DO X114:9
)
• zero speed limit for activating the drive STO: 90 rpm
90 rpm
)
• delay for activating STO after the zero speed limit has been reached: 0 ms
SS1-r ramp zero speed delay for STO
=
0 ms
)
• speed limit activated brake not in use
=
0 ms
).
• See also section
on page
.