The values can be set to any level percentage associated with the quartz level sense
increments, including all the same value. For example, LEVEL 1 relay output could be
set to any value above, below or equal to any other LEVEL relay output.
To remain backwards compatible with the existing design, the LOW CHEM LEVEL is
the only signal in this screen that is an alarm. This signal has the same flexible
features as the other four levels, but it is linked to the “ANY” ALARM output and will
show up on the LCD.
NOTE
:
The lowest value that can be entered for LOW CHEM LEVEL is 23.
Using the right (or left) arrow keypad will scroll through the other setup
parameters.
Pressing X will prompt the user to save the changes or leave parameters unchanged.
5.7.4
LCD Display Controls
The user has the ability to set the contrast and brightness of the LCD display. Factory
setting is preset for optimal settings; however the user may adjust if required.
L C D
C O N T R A S T
1 6
L C D
B A C K L I
G H T
5 0
5.7.5
Buzzer
B U Z Z E R
O F F
N O W
E N T E R
T O
C H A N G E
B U Z Z E R
O N
N O W
E N T E R
T O
C H A N G E