LubriMist
®
Model IVT
Oil Mist Generating System
Installation and Operating Manual
Page 144
of 256
Push the
SET
key again. The display will show the current
BANDWIDTH
and the rightmost digit
will display “b”
.
The
UP
and
DOWN
keys will adjust the bandwidth between the limits of 0.5F and
20.0F (or equivalent degrees C, if F/C parameter is set to C). Bandwidth is the effective gain of
the controller. A small bandwidth will approach on-off type control while a large bandwidth will
accommodate thermal systems with more time lag. Pushing
SET
again will advance to the next
parameter, but if no key is pushed for 10 seconds, the control will automatically return to the
temperature display and control screen.
Push the
SET
key again. The display will show the current temperature cutoff setpoint and the
rightmost digit will display “2”
.
The
UP
and
DOWN
arrow keys will adjust the temperature cutoff
setpoint between the limits of 100F and 190F (or equivalent degrees C, if F/C parameter is set to
C). Pushing
SET
again will advance to the next parameter, but if no key is pushed for 10
seconds, the control will automatically return to the temperature display and control screen.
Push the
SET
key again. The display will show the current alarm setpoint and the rightmost digit
will display “3”
.
The
UP
and
DOWN
arrow keys will adjust the alarm setpoint between the limits of
60F and 100F (or equivalent degrees C if F/C Jumper is ON). Pushing
SET
again will advance to
the next parameter, but if no key is pushed for 10 seconds, the control will automatically return to
the temperature display and control screen.
Push the
SET
key again. The display will show the current temperature display units and the
rightmost digit will display “U”
.
The
UP
and
DOWN
arrow keys will toggle the display units
between FAH and CEL. Pushing
SET
again will advance to the temperature display and control
screen, but if no key is pushed for 10 seconds, the control will automatically return to this screen
anyway.
The air / oil heater will now resume control at the new control and alarm settings.
Use SET Key To Navigate Between
Screens
UP Key Increases Values
DOWN Key Decreases Values
“ALARM” LED Illuminates
1)
For High Temperature Alarm
2)
For Low Temperature Alarm
3)
When Setting Low Temperature
Setting In Program Mode.
Temperature Values Are Indicated On LED
Readout
In The Normal Mode, The Temperature
Units Are Displayed
F = Fahrenheit
C = Celsius
In Program Mode The Function Variable Is
Displayed
1= Control Temperature Setting
2= High Temperature Cutout Setting
3= Low Temperature Alarm Setting
b= Bandwidth Settings
SET
*
1
2
Illuminates When The High Temperature
Cutout Setting Is Being Displayed
Illuminates When The Control Temperature
Setting Is Being Displayed
Содержание LubriMist IVT
Страница 22: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 22 of 256...
Страница 63: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 63 of 256...
Страница 81: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 81 of 256 OPERATING GUIDE...
Страница 148: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page148 of 256...
Страница 149: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page149 of 256 CONTROLLING THE MIST...
Страница 152: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page152 of 256...
Страница 161: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page161 of 256 TROUBLE SHOOTING GUIDE...
Страница 204: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 204 of 256 IVT Front Cabinet Door...
Страница 208: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 208 of 256 IVT Cabinet Rear...
Страница 236: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 236 of 256 Air Supply Components...
Страница 245: ...LubriMist Model IVT Oil Mist Generating System Installation and Operating Manual Page 245 of 256 Air Supply Components...