NORDAC
PRO
(SK 500P) – Manual with installation instructions
46
BU 0600 en-3221
M
3~
PE U V W +B -B -DC
PE L3 L2 L1
L1 / L
L2 / N
L3 / -
PE
M
3~
PE U V W +B -B -DC
PE L3 L2 L1
Coupling if
FIs ready
Ready
message from
all FIs
U1
U2
Figure 3: Illustration of a DC-coupling
1 The link circuits of the individual frequency inverters must be protected with suitable fuses.
2
NOTICE!
Ensure that the coupling is only made after readiness is reported. Otherwise, there is
a danger that all the frequency inverters will be charged by a single device.
3 Ensure that the coupling is disconnected as soon as one of the devices is no longer ready for
operation.
4 For high availability, a braking resistor must be used. If different sizes of frequency inverters are
used, the braking resistor must be connected to the larger of the two frequency inverters.
5 If devices with the same rating (identical type) are coupled, and the same mains impedances
are in effect (identical lengths of cable to the mains rail), the frequency inverters may be
operated without mains chokes. Otherwise a mains choke must be installed in the mains cable
of each frequency inverter.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...