5 Parameter
BU 0600 en-3221
177
P551
Drive profile
S
Setting range
0 … 3
Factory setting
{ 0 }
Description
Activation of a process data profile.
Setting values
Value
Meaning
0
USS
No specific drive profile.
1
CANopen DS402
CANopen drive profile according to DS402.
2
Reserve
3
Nord-Custom
Drive profile with freely assignable bits.
Note:
The free bits are set via parameters
P480 / P481
P551{ 3} Free bit assignment in the control and status word for NORD custom
Control word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
P480
P480
P480
P480
P480
P480
P480
P480
FR
P2
P1
SPE
EO
QS
EV
SO
[-07]
[-06]
[-05]
[-04]
[-03]
[-02]
[-01]
[-00]
SO
= Switched On
EV
= Enable Voltage
QS
= Quick Stop
EO
= Enable Operation
SPE
= Setpoint Enable
P1 / P2
= Parameter Set Switch
FR
= Fault Reset
P480
[0…7]
= NORD User Bit
Status word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
P481
P481
P481
P481
P481
P481
P481
P481
WARN
P2
P1
TARG
FAULT
QS
OE
RTSO
[-07]
[-06]
[-05]
[-04]
[-03]
[-02]
[-01]
[-00]
RTSO
= Ready To Switch On
OE
= Operation Enabled
QS
= Quick Stop
FAULT
= Error occurred
TARG
= Target Reached
P1 / P2
= Current Parameter Set
WARN
= Warning
P481
[0…7]
= NORD User Bit
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...