5 Parameter
BU 0600 en-3221
193
Information
If the mains voltage is not connected (X1) the following parameter shows the value 0 and not the
actual correct operating value.
P739
Temperature
Display range
-40 ... 150 °C
Arrays
[-01] = Heat sink
Actual temperature of the heat sink.
This value is used for overtemperature switch-off
E001.0
[-02] = Ambient temperature
UZW
Actual temperature of the interior of the power
section of the inverter. This value is the basis for
overtemperature switch-off
E001.1.
[-03] = Motor KTY:
Displays the actual motor temperature when
monitoring with a temperature sensor.
[-04] = Microcontroller
Actual temperature of the microprocessor in the
control section of the inverter. This value is the
basis for overtemperature switch-off
E001.1.
Description
Displays the actual temperature values at various measuring points.