E016
16.1
Magn. current watch
Required exciting current not achieved at moment of switch-
on.
•
Check connections and cables on both sides
•
Check the motor
Further notes:
•
Check (
P539
)
•
Check motor data (
P201
…
P209
)
E016
16.2
Change phase direct.
The motor phase sequence (U – V – W) has been changed
during operation (enable).
Further notes:
•
Check parameter values in (
P583
)
•
Has parameter set (
P100
) been switched over?
E017
17.0
Change assembly grp.
The customer unit (SK CU5-…) is not recognised by the
frequency inverter.
•
Check the fastening of the customer unit / contacts
•
EMC faults
Check cable shielding and earthing terminals of electrical
components.
E018
18.0
Safety circuit
The Safe Pulse Block safety circuit has triggered during
release.
E018
18.5
Safety SS1
The parameterised trigger time (
P423
) of the SS1-t
functionality has expired. STO is triggered as the inverter
still sends output pulses.
This error cannot be acknowledged. Restart the frequency
inverter (Power Off
120 s
Power On).
E018
18.6
Safety system
Safety function error: This error cannot be acknowledged.
E019
19.0
Parameter ident.
Automatic identification of the connected motor has failed.
•
Check connections and cables on both sides
•
Check the motor
Further notes:
•
Check motor data (
P201
…
P209
)
E019
19.1
Rotor position
Incorrect result for motor position identification by test signal
method.
E019
19.2
Rotor pos. North/South
Incorrect result for motor position identification by test signal
method
E022
---
Reserved
PLC error message
E023
---
Reserved
PLC error message
E024
---
Reserved
PLC error message
E025
---
Reserved
POSICON
error message see supplementary manual BU
0610
E026
---
microSD card error
MicroSD card data cannot be read.
•
Repeat data transfer.
•
Check data format (.nsdx).
•
Use original microSD card (Part No.: 275292200).
E090
90.0
System error
Unknown error code from sub system. The FI has received
an error code from an external unknown module. FI update
required. The new, extended error code can be read from
P700 [-04]
. This allows the error to be distinguished.
•
Restart device
E091
91.0
Update error
Update failed
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...