5 Parameter
BU 0600 en-3221
185
P704
Volt. last error
S
Display range
0... 500 V AC
Arrays
[-01] … [-10]
Description
“
Last voltage error 1
… 10
”. This parameter stores the output voltage that was being
delivered at the time the fault occurred. The values of the last 10 errors are stored.
P705
Dc.lnk volt. last er.
S
Display range
0 ... 1000 V DC
Arrays
[-01] … [-10]
Description
"
Link circuit voltage last error 1
… 10
“. This parameter stores the link circuit voltage
that was being delivered at the time the error occurred. The values of the last 10
errors are stored.
P706
P set last error
S
Display range
0 ... 3
Arrays
[-01] … [-10]
Description
“
Parameter set last error 1
… 10
”. This parameter stores the parameter set code that
was active when the error occurred. Data for the previous 10 faults are stored.
P707
Software version
Display range
0.0 ... 9999.9
Arrays
[-01] = IO Version
[-02] =
IO Revision
[-03] = IO Special version
[-04] = RG Version
[-05] = RG Revision
[-06] = RG Special version
[-07] = IO Loader Version
[-08] = RG Loader Version
[-09] = FW update File version
Description
“
Software version
/
Revision
”. This parameter shows the software and revision numbers
in the FI. This can be significant when different FIs are assigned the same settings.
Array [-03] provides information about any special versions of the hardware or
software A zero stands for the standard version.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...