5 Parameter
BU 0600 en-3221
163
P514
CAN baud rate
Setting range
0 … 7
Factory setting
{ 5 }
Description
Used to set the transfer rate (transfer speed) via the CAN bus interface. All bus
participants must be set to the same baud rate.
Setting values
Value
Meaning
Value
Meaning
Value
Meaning
0
10 kBaud
3
100 kBaud
6
500 kBaud
1
20 kBaud
4
125 kBaud
7
1 MBaud
1)
(Only for test purposes)
2
50 kBaud
5
250 kBaud
1)
Reliable operation cannot be guaranteed.
P515
CAN bus address
Setting range
0 … 255
Arrays
[-01] = Slave address
Receipt address for CAN and CANopen system bus
[-02] = Broadcast slave
address
Broadcast receipt address for CANopen system bus
(slave)
[-03] = Master address
Broadcast transmission address for CANopen
system bus (Master)
Factory setting
All { 32 }
Description
Setting of the basic CANbus address for CAN and CANopen.
Note
If several frequency inverters are to communicate with each other via the system bus,
the addresses must be set as follows: FI 1 = 32, FI 2 = 34 … .
P516
Skip frequency 1
S
P
Setting range
0.0 … 400.0 Hz
Factory setting
{ 0.0 }
Description
The output frequency around the frequency in the range between
+P517
and
-P517
set here is not displayed.
This range is transmitted with the set deceleration and acceleration ramp; it cannot be
continuously supplied to the output.
Note
Frequencies below the absolute minimum frequency should not be set.
Setting values
0.0
Skip frequency inactive
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...