5 Parameter
BU 0600 en-3221
129
P401
Analog input mode
S
Setting range
0 … 5
Arrays
[-01] = Analog input 1
Analogue input 1 (AI1) integrated into the FI
[-02] = Analog input 2
Analogue input 2 (AI2) integrated into the FI
[-03] = Ext. analog input 1
"External analog input 1".
Analogue input 1 of the
first IO extension
[-04] = Ext. analog input 2
"External analog input 2".
Analogue input 2 of the
first IO extension
[-05] = Ext. A. in.1 2.IOE
"External analog input 1 of the 2nd IOE”.
Analogue
input 1 of the second I/O extension
[-06] = Ext. A. in.1 2.IOE
"External analog input 2 of the 2nd IOE”.
Analogue
input 2 of the second I/O extension
[-07] = Reserved
[-08] = Reserved
[-09] = Clock input 1
Scope of application
[-01] … [-02]
SK 500P and higher
[-03] … [-09]
SK 530P and higher
Factory setting
All { 0 }
Description
"
Analog input mode
". This parameter determines how the frequency inverter is to
respond to an analogue signal which is less than the 0 % adjustment (
P402
).
Setting values
Value
Function
Description
0
limited to 0-100%:
An analogue setpoint smaller than the programmed adjustment
0 % (
P402
) does not result in undershooting of the programmed
minimum frequency
P104
, i.e. it does not result in a change of the
direction of rotation.
1
0 – 100 %
If a setpoint smaller than the programmed adjustment 0 % (
P402
)
is present, this can cause a change in direction rotation. This
allows rotation direction reversal using a simple voltage source and
potentiometer.
E.g. internal setpoint with reversal of direction of rotation:
P402 = 50 %
,
P104 = 0 Hz
, Potentiometer 0 – 10 V
Rotation
direction change at 5 V in mid-range setting of the potentiometer.
At the moment of reversing (
hysteresis = ± P505
) the drive is at a
standstill if the minimum frequency
P104
is smaller than the
absolute minimum frequency
P505
. A brake that is controlled by
the FI will be applied in the hysteresis range.
If the minimum frequency
P104
is greater than the absolute
minimum frequency
P505
, the drive reverses when the minimum
frequency is reached. In the hysteresis range
± P104
, the FI
supplies the minimum frequency
P104
; the brake controlled by the
FI is not applied.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...