6 Operating status messages
BU 0600 en-3221
205
6.2 Messages
Error messages
Display in the
SimpleBox / ControlBox
Fault
Text in the ParameterBox
Cause
•
Remedy
Group
Details in P700
[-01] / P701
E001
1.0
Inverter overtemp.
Temperature monitoring of the inverter
Temperature range has been exceeded or undershot.
•
Reduce or increase ambient temperature
•
Check fan or cabinet ventilation
•
Check the device for dirt
Further notes:
•
see (
P739)
for temperature display
E001
1.1
Intern. inverter temp
Temperature monitoring of the inverter
Temperature range has been exceeded or undershot.
•
Reduce or increase ambient temperature
•
Check fan or cabinet ventilation
•
Check the device for dirt
Further notes:
•
see (
P739
) for temperature display
E002
2.0
Motor overtemp. - PTC
The motor temperature sensor (PTC) or the separate PTC
input (X4) has triggered.
•
Reduce motor load
•
Increase motor speed
•
Install external motor fan or check the function
Further notes:
•
Check parameter setting (
P425
)
E002
2.1
Motor overtemp.I²t
The inverter has detected an impermissible motor
temperature (motor I
2
t).
•
Reduce motor load
•
Increase motor speed
•
Repeat stator resistance measurement (Chap. 5.1.4
"Motor data / characteristic curve parameters")
E002
2.2
Dig In overtemp.
Thermostat (e.g. from braking resistor) has been triggered.
The digital input is “low”.
•
Check connection and thermostat
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...