NORDAC
PRO
(SK 500P) – Manual with installation instructions
62
BU 0600 en-3221
3.2.2 Display
3.2.2.1
Displays
1
Inverter load display (with 100% value)
2
Parameter set display
3
Five digit 7-segment display with prefix and 4 x point
4
Three digit 14-segment display for units
5
Enable right and enable left
6
4 Inverter status displays
3.2.2.2
Operation
5-digit,
7-segment
LED display
Operating mode
Display
Comment
Ready for
operation without
setpoint present
If the underscores flash slowly the frequency
inverter is not ready for operation:
•
Switch-on inhibit: Function “safe pulse block“
or "quick stop active"
•
Enable signal present before the frequency
inverter is ready for operation.
In operation
Numerical display
Display of the operating value (e.g. Actual
frequency) selected in parameter
P001
In case of a
warning
The actual operating display remains until the
background changes to yellow.
In case of fault
Displays the present
fault message. Display
lights up red.
Slow flashing of the display indicates that the fault
is no longer present and the error message can
be acknowledged.
Parameterisation
Parameter value
Parameter group:
Example motor data (P2 - -)
Parameter number:
Example nominal speed (
P202
)
Parameter value
Example: 1360 rpm
PASS flashes if password protection is enabled in
P004. The parameter settings are not saved.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...