5 Parameter
BU 0600 en-3221
181
P558
Flux delay
S
P
Setting range
0, 1, 2... 5000 ms
Factory setting
{ 1 }
Description
ASM
The ISD control can only function correctly if there is a magnetic field in the
motor. For this reason, a DC current is applied before starting the motor to
provide excitation of the stator winding. The duration depends on the size of
the motor and is automatically set in the factory setting of the FI. For time-
critical applications the flux delay can be set or disabled.
PMSM
When used with PMSM, the dwell time can be set via this parameter during
rotor position identification using the dwell method. Total dwell duration = 2.5
x P558 [ms]
Note
Setting values that are too low can reduce the dynamics and starting torque.
Setting values
Value
Meaning
0
Switched off
1
Automatic calculation
2 … 5000
Time set in [ms]
P559
DC run-on time
S
P
Setting range
0.00 ... 30.00 sec
Factory setting
{ 0.50 }
Description
After a stop signal and elapse of the brake ramp, direct current is applied to the motor
for a short time. This should completely stop the drive. Depending on the inertia, the
time for which the current is applied can be set in this parameter.
The current level depends on the previous braking procedure (current vector control)
or the static boost (linear characteristic).
P560
Parameter, Saving mode
S
Setting range
0 … 2
Factory setting
{ 1 }
Description
"
Parameter saving mode
".
Note
If BUS communication is used to implement parameter changes, it must be ensured
that the maximum number of write cycles to the EEPROM (100,000 x) is not
exceeded.
Setting values
Value
Meaning
0
Only in RAM
Changes to the parameter settings are not written to the EEPROM.
All saved settings which were made before changing the saving
mode are retained, even if the FI is disconnected from the mains.
1
RAM and EEPROM
All parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the
mains supply.
2
OFF
Saving in RAM and EEPROM not possible. (No parameter changes
are adopted)
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...