5 Parameter
BU 0600 en-3221
99
P103
Deceleration time
P
Setting range
0.00 … 320.00 s
Factory setting
{ 2.00 }
Description
The deceleration time is the time corresponding to the linear frequency reduction from
the set maximum frequency
P105
to 0 Hz. If an actual setpoint <100 % is being used,
the deceleration time reduces accordingly.
The deceleration time can be extended by certain circumstances, e.g. by the selected
“Disconnection mode”
P108
or
“Ramp smoothing”
P106
.
Note
Care must be taken that the parameter values are realistic. The setting
P103 = 0
is
not permissible for the drive units!
Notes on ramp gradient
: see
P102
P104
Minimum frequency
P
Setting range
0.0 … 400.0 Hz
Factory setting
{ 0.0 }
Description
The minimum frequency is the frequency supplied by the FI as soon as it is enabled
and no additional setpoint is set.
In combination with other setpoints (e.g. analogue setpoint or fixed frequencies) these
are added to the set minimum frequency.
This frequency is undershot when
•
The drive is accelerated from standstill.
•
The FI is blocked. The frequency then reduces to the absolute minimum frequency
P505
before it is blocked.
•
The FI reverses. Reversal of the rotation field takes place at the absolute minimum
frequency
P505
.
This frequency can be continuously undershot if the function
"Maintain the freq.”
(digital input function = 9) was executed during acceleration or deceleration.
P105
Maximum frequency
P
Setting range
0.1 … 400.0 Hz
Factory setting
{ 50.0 }
Description
The maximum frequency is the frequency supplied by the FI after being enabled and
once the maximum setpoint is present (e.g. analogue setpoint according to
P403
, a
correspondingly fixed frequency or maximum via a ParameterBox).
This frequency can only be exceeded by the slip compensation
P212
, the function
“Maintain the freq.”
(digital input function = 9) and the switch to another parameter set
with lower maximum frequency.
Maximum frequencies are subject to certain restrictions, e.g.
•
Restrictions in weak field operation,
•
Compliance with mechanically permissible speeds,
•
PMSM: Restriction of the maximum frequency to a value which is slightly above
the nominal frequency. This value is calculated from the motor data and the input
voltage.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...