(SK 500P) – Manual with installation instructions
128
BU 0600 en-3221
06
Current limit
Based on the set current limit
P536
, this can be changed via the
analogue input.
07
Maximum frequency
The maximum frequency of the FI is varied. 100 % corresponds to
the setting in parameter
P411
. 0 % corresponds to the setting in
parameter
P410
. The values for the min./max. output frequency
P104 / P105
cannot be exceeded or undershot.
08
Actual PID frequency limited
1)
As for function {3},
“Actual frequency PID”
, however the output
frequency cannot fall below the programmed "minimum frequency"
value in Parameter
P104
(no reversal of direction of rotation).
09
Actual frequency PID monitored
1)
As for Function {3},
“Actual frequency PID”
, however the FI
switches the output frequency off when the minimum frequency
P104
is reached.
10
Servo mode torque
In the
“CFC closed
-
loop“
control method (
P300 = 1
) the motor
torque can be set or limited with this function. Here the speed
regulation is switched off and a torque control is activated. The
analogue input is then the source of the setpoint.
In the open-loop method (
P300
≠
1
) this function can be used with
reduced control quality.
11
Torque precontrol
This function enables a value for the anticipated torque
requirement to entered in the controller (interference factor
switching). This function can be used to improve the load take-up
of lifting equipment with separate load detection.
12
Reserved
13
Multiplication
The setpoint is multiplied by the analogue value supplied. The
analogue value adjusted to 100 % then corresponds to a
multiplication factor of 1.
14
Actual value process controller
1)
Activates the process controller. Activates the process controller,
analogue input 1 is connected to the actual value sensor
(compensator, air can, flow volume meter, etc.). The mode (0-10 V
or 0/4-20 mA) is set in
P401
.
15
Process controller setpoint
1)
As for Function {14}, however the setpoint is specified (e.g. by a
potentiometer). The actual value must be specified using another
input.
16
Process controller precontrol
1)
Adds an adjustable additional setpoint after the process controller
17
Reserved
18
Curve travel calculator
The slave communicates the actual speed to the master. From its
own speed, the speed of the slave and the specified speed, the
master calculates the actual setpoint speed. Therefore neither of
the two drives moves faster than the specified speed in the curve.
19
Reserved
20
Set analog output
Value from
P542
21
... 45 Reserved
46
Process controller
torque setpoint
47
Gear ratio factor
Sets the speed ratio between master and slave
48
Motor temperature
Motor temperature measurement with temperature sensor (e.g.
KTY-84), see Section (Chap. 4.4)for details.
49
Ramp time
Acceleration and deceleration
53
d-correction, F process
"Diameter correction, PID process controller frequency"
54
d-correction Torque
"Diameter correction, torque"
55
d-correction, F+torque
"Diameter correction, PID process controller frequency and torque"
56
Acceleration time
Adjustment of the time for the acceleration process. 0 % corresponds
to the shortest time possible, 100% corresponds to
P102
57
Deceleration time
Adaptation of the time for the deceleration process. 0 % corresponds
to the shortest time possible, 100% corresponds to
P103
58
Reserved for POSICON
1)
Process controller details: P400 and "Process controller".
2)
The limits of these values are set by parameter
P410
“Minimal frequency auxiliary setpoints”
and
parameter
P411
“Maximum frequency auxiliary setpoints”
.
Note:
Overview of scaling in (Chap. 8.8).
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...