NORDAC
PRO
(SK 500P) – Manual with installation instructions
130
BU 0600 en-3221
2
0 – 10V monitored:
If the minimum adjusted setpoint
P402
is undershot by 10 % of the
difference value from
P403
and P402, the FI output switches off.
Once the setpoint is greater than
P402 -
(10 % * (
P403
…
P402
)), it
will deliver an output signal.
Note
: A function for the relevant input
must be assigned in
P400
.
E.g. Setpoint 4 - 20 mA:
P402
: “Adjustment 0 % “= Setting 20 %;
P403
: "Adjustment 100 %“ = Setting 100%; 10 % of the difference
between
P403
and
P402
corresponds to 0.8 V; i.e. 2 V...10 V
(4 ... 20 mA) = normal operating range, 0.8 V ... 2 V = Minimum
frequency setpoint less than 0.8 V (2.4 mA) causes the output to
switch off.
3
- 100 % – 100 %
If a setpoint smaller than the programmed “adjustment 0 % “(
P402
)
is present, this may cause a change in direction rotation. This
allows rotation direction reversal using a simple voltage source and
potentiometer.
E.g. internal setpoint with reversal of direction of rotation:
P402 = 50 %
,
P104 = 0 Hz
, Potentiometer 0 – 10 V. Rotation
direction change at 5 V in mid-range setting of the potentiometer.
At the moment of reversing (hysteresis = ± P505) the drive is at a
standstill if the minimum frequency
P104
is smaller than the
absolute minimum frequency
P505
. A brake which is controlled by
the FI has not been applied in the hysteresis range.
If the minimum frequency
P104
is greater than the absolute
minimum frequency
P505
, the drive reverses when the minimum
frequency is reached. In the hysteresis range
± P104
, the FI
supplies the minimum frequency
P104
; the brake controlled by the
FI is not applied.
NOTE
: The function -10V – 10V is a description of the method of
function and not a reference to a physical bipolar signal (see
example above).
4
0 – 100 % with error 1
"
0 –
100 % with shutdown on
error 1
“. If the value of the 0 %
adjustment in
P402
is undershot, the error message
E12.8
"
Undershoot of Analog In Min
" is activated. If the value of the
100 % adjustment in
P403
is exceeded, the error message
E12.9
Analog In Max exceeded
is activated. Even if the analogue value is
outside the limits defined in
P402
and
P403
, the setpoint value is
limited to 0 - 100 %.
The monitoring function only becomes active if an enable signal is
present and the analogue value has reached the valid range
(
≥
P402
or.
≤
P403
) for the first time (e.g. pressure build-up after
switching on a pump).
Once the function has been activated, it also operates if actuation
takes place via a field bus, for example, and the analogue input is
not actuated.
5
0 – 100 % with error 2
"
0 – 100
% with shutdown on error 2
“:
See setting {4 } ("0 – 10% with error switch off 1“), however:
In this setting the monitoring function only becomes active if an
enable signal is present and the time during which the error
monitoring is suppressed has elapsed. This suppression time is set
in parameter
P216
.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...