NORDAC
PRO
(SK 500P) – Manual with installation instructions
166
BU 0600 en-3221
P522
Flying start offset
S
P
Setting range
-10.0 … 10.0 Hz
Factory setting
{ 0.0 }
Description
"
Flying start offset
“. A frequency value that can be added to the frequency value
found, e.g. to remain in the motor range and so avoid the generator range and
therefore the chopper range.
P523
Factory setting
Setting range
0 ... 3
Factory setting
{ 0 }
Description
With the selection and activation of the relevant value, the selected parameter range
is set to the factory setting. Once this setting is made, the parameter value
automatically changes back to 0.
Note
With the setting
“Load factory settings”
the safety-relevant parameters
P423
,
P424
,
P499
are not reset. These must be reset manually.
Setting values
Value
Meaning
0
No change
Does not change the parameterisation.
1
Load factory setting
“Load factory setting”. The entire parameterisation of the FI is reset
to the factory setting. All originally parameterised data are lost.
2
Fact.setng.w.out bus
“Load factory setting without bus”.
All FI parameters, however
not
the CAN-, CANopen-, USS-, and system bus parameters are reset
to the factory setting (including Ethernet).
3
Fact. without motor data
“Load factory setting without motor
parameter”.
All parameters of
the frequency inverter, with the
exception
of the motor data, are
reset to the factory setting.
4
Fact.set only Ethernet
“Load factory settings, only Ethernet parameters”.
Only the FI
parameters for the Ethernet settings are reset to the factory setting
P525
Load monitoring max
S
P
Setting range
1 ... 400 % / 401
Arrays
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Factory setting
All { 401 }
Description
"
Load monitoring maximum value
“. Setting of the upper limit of load monitoring. Up to
3 values can be specified. Prefixes are not taken into account, only the integer values
are processed (motor / generator torque, right/left rotation). The array elements
[-01]
,
[-02]
and
[-03]
of parameters
P525 … P527
, or the entries which are made there
always belong together.
Note
Setting
401 = Off
Monitoring is not performed.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...