NORDAC
PRO
(SK 500P) – Manual with installation instructions
96
BU 0600 en-3221
P063
606D & 606E Velocity window
!
S
Setting range
[-01] = 0 … 24000 rpm
[-02] = 0 … 32767 ms
Arrays
[-01] = 606D Velocity window
[-02] = 606E Velocity window time
Factory setting
[-01] = { 100 }
[-02] = { 200 }
PDO mapping
[-01] = No
[-02] = No
Data type
[-01] = UNSIGNED 16 Bit
[-02] = UNSIGNED 16 Bit
Description
[-01] =
DS42 object 606Dh: Permissible deviation of the actual speed relative to the
target speed in which the speed is considered to have been reached. Applies
for “Profile Velocity” mode.
[-02] =
DS42 object 6068h: Dwell time in the target window so that the target velocity
is considered to have been reached. Applies for “Profile Velocity” mode.
Description
Sets time window for velocity and time
P064
606F & 6070 Velocity thresh
!
S
Arrays
[-01] =
606F Velocity threshold
value
[-02] = 6070 Velocity threshold value
Setting range
[-01] = 0 … 24000 rpm
[-02] = 0 … 32767 ms
Factory setting
[-01] = { 100 }
[-02] = { 200 }
PDO mapping
[-01] = No
[-02] = No
Data type
[-01] = UNSIGNED 16 Bit
[-02] = UNSIGNED 16 Bit
Description
[-01] =
DS42 object 606Fh: Permissible deviation of the actual velocity relative to
velocity zero. If the drive undershoots this threshold value beyond the dwell
time, Bit 12 of the status word is set. Applies for “Profile Velocity” operating
mode.
[-02] =
DS42 object 6070h: Dwell time below the threshold value until Bit 12 “Drive
stopped” is set. Applies for “Profile Velocity” mode.
P065
6083 Acc. profile
S
Setting range
0... 2147483647 rpm/s
Factory setting
{ 750 }
PDO mapping
RxPDO
Data type
UNSIGNED 32 Bit
Description
DS402 object 6083h: Acceleration in “Profile Position” and “Profile Velocity” modes.
P066
6084 Decel. profile
S
Setting range
0... 2147483647 rpm/s
Factory setting
{ 750 }
PDO mapping
RyPDO
Data type
UNSIGNED 32 Bit
Description
DS402 object 6084h: Deceleration in “Profile Position” and “Profile Velocity” modes.
P067
6085 Quick Stop. decel.
S
Setting range
0... 2147483647 rpm/s
Factory setting
{ 15000 }
PDO mapping
RxPDO
Data type
UNSIGNED 32 Bit
Description
DS402 object 6085h: Quick stop deceleration in “Profile Position” and “Profile
Velocity” modes.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...