NORDAC
PRO
(SK 500P) – Manual with installation instructions
112
BU 0600 en-3221
P219
Auto. flux adjustment
S
Setting range
25 ... 100 % / 101
Factory setting
{ 100 }
Description
"
Automatic magn. adjustment
". With this parameter, the magnetic flux of the motor
can be automatically matched to the motor load, so that the energy consumption is
reduced to the amount which is actually required.
P219
is the limiting value, to which
the field in the motor can be reduced.
Reduction of the field is performed with a time constant of 7.5 s. If the load increases,
the field is increased with a time constant of approx. 300 ms. The field is reduced so
that the magnetisation current and the torque current are approximately equal, i.e. the
motor is operated with “optimum efficiency”.
This function is suitable for applications with relatively constant torque (e.g. pump and
fan applications). Its effect therefore replaces a quadratic curve, as it adapts the
voltage to the load.
Note
For applications with rapid torque fluctuations (e.g. lifting equipment) this parameter
should be left at the factory setting (100%). Otherwise, rapid load changes could
cause shut-down due to overcurrent or "breakdown".
This parameter does not function with synchronous motors (IE4 motors).
Setting values
Value
Meaning
100
Function disabled
101
Automatic
Activation of automatic excitation current control. The ISD controller
then operates with a subordinate flux controller, which improves the
slippage calculation, especially at higher loads. The control times
are considerably faster than with normal ISD control
P219 = 100
.
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...