5 Parameter
BU 0600 en-3221
145
Information
For the following parameter
P434
all functions are disabled or 0V is output unless the mains voltage
(X1) is applied. This does not include the following functions: {7}, {8}, {12}, {30} – {37}, {38} and {50} –
{59}.
P434
Digital out function
P
Setting range
0 … 59
Arrays
[-01] = Binary output.1 / MFR1 Multi-function relay 1 (K1) integrated into the FI
[-02] = Binary output.2 / MFR2 Multi-function relay 2 (K2) integrated into the FI
[-03] = Digital output 1
Digital output 1 (DO1) integrated into the FI
[-04] = Digital output 2
Digital output 2 (DO2) integrated into the FI
[-05] = Digital output 3
Digital output 1 (DIO1) integrated into SK CU5
[-06] = Digital output 4
Digital output 2 (DIO2) integrated into SK CU5
[-07] = Digital output 5
Digital output 3 (DIO3) integrated into SK CU5
[-08] = Digital output 6
Digital output 4 (DIO4) integrated into SK CU5
[-09] = Digital function
Analog1
Digital output 1 (AO1) (digital function) integrated
into the FI
[-10] = Reserve
[-11] = Digital function Analog3 Analogue output 3 (AO3) (IOE) (digital function)
[-12] = Digital function Analog4 Analogue output 4 (AO4) (IOE) (digital function)
Scope of application
[-01] … [-02]
SK 500P and higher
[-03] … [-08]
SK 530P and higher
[-09] … [-10]
SK 500P and higher
[-11] … [-12]
SK 530P and higher
Factory setting
[-01] = { 1 }
[-02] = { 7 }
All other { 0 }
Description
“
Digital output function
“. Up to 10 outputs (2 of which are relays) are available. These can
be freely programmed with digital functions. These can be seen in the following table.
Note
With settings 3 to 5 and 11 the two relays (K1, K2) work with 10 % hysteresis, i.e. the
relay contact closes (setting 11: opens) on reaching the limiting value and opens
(setting 11: closes) if a 10 % lower value is undershot. This behaviour can be inverted
with a negative value in
P435
.
Alternatively, digital outputs 3… 6 can also be used as digital inputs 7… 10 (see
P420
).
For these inputs/outputs it is recommended to parameterise either an input or an
output function. However, if an input function and an output function are
parameterised, a High signal from the output function will result in activation of the
input function. This IO connection is hence used as a kind of "flag".
Setting values
Value
Description
Signal
00
No function
Input switched off.
Low
01
External brake
For control of a mechanical brake on the motor. The
relay switches at a programmed absolute minimum
frequency
P505
. For typical brakes a setpoint delay of
0.2 ... 0.3 s (see
P107
) should be programmed.
A mechanical brake can be directly switched with AC.
(Note the technical specification of the relay contact!)
High
02
Inverter is working
The closed relay contact indicates voltage at the inverter
output (U - V - W) (as well as DC run-on
P559
).
High
03
Current limit
Based on the nominal motor current setting in
P203
. This
value can be adjusted with scaling
P435
.
High
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...