4 Commissioning
BU 0600 en-3221
73
4.3 Minimum configuration of control connections
If the frequency inverter is to be controlled via the digital and analogue inputs, this can be
implemented immediately in the condition as delivered. Settings are not necessary for the moment.
Minimum circuitry
Basic parameters
If the current setting of the frequency inverter is not known, loading the default setting is
recommended
P523 = 1
. The inverter is pre-programmed for standard applications in this
configuration. If necessary the following parameters can be changed with the optional ControlBox
SK TU5-CTR.
P 0 - -
Display
parameters
_ _ _ _ _
P 1 - -
Basic parameters
P 2 - -
Motor data
P 4 - -
Control terminals
P 5 - -
Additional
parameters
P 7 - -
Information
B
y def
ault
t
he ac
tual
out
put
f
re
q
ue
nc
y
is
dis
play
ed
P 1 0 2
Acceleration time
0 ... 320s
M
ot
or
da
ta
P 4 0 0
Function Analogue input
0...10V frequency
Operating value display
(or operational)
following mains ON
P 1 0 3
Deceleration time
0 ... 320s
P 1 0 4
Min. frequency
0 ... 400Hz
P 1 0 5
Max. frequency
0.1 ... 400Hz
P 4 2 0
Function Digital input 1
ON right
P 5 2 3
=1
Load factory data
Potentiometer, 10 kOhm
(Function P400 [-01] = 1)
(min./max. Range = P104/105
Switch, ON/OFF
(Function P420 [-01]= 1)
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...