5 Parameter
BU 0600 en-3221
141
45
3-W-Ctrl.Start-Right
(closing switch for
enable right)
"
3
-
Wire
-
Control
". This control function provides an alternative to
enable R/L{01, 02}, for which permanently applied levels are
required.
Here, only a control pulse is required to trigger the function.
Control of the FI can therefore be performed entirely with keys.
A pulse on the function
“Reverse direction of rotation”
(see
Function 65) inverts the present direction of rotation. This
function is reset with a "Stop signal" or by activating a key for
the functions {45, 46, 49}.
0
1
Flank
46
3-W-Ctrl.Start-Left
(closing key for enable Left)
0
1
Flank
49
3-Wire-Ctrl.Stop
(opening key for Stop)
0
1
Flank
47
Motorpot. Freq. +
In combination with enable R/L the output frequency can be
continuously varied. To save a current value in
P113
, both
inputs must have a High voltage for 1.5 s. This value is then
used as the next starting value for the same direction of rotation
(Enable R/L) otherwise start at f
MIN
. Values from other setpoint
sources (e.g. fixed frequencies) are not taken into account.
High
48
Motorpot. Freq. -
High
50
Bit0 fixedfreq.Array
Fixed frequency array, binary coded digital inputs to generate
up to 32 fixed frequencies.
P465 [-01] ... [-31]
High
51
Bit 1 fixedfreq.Array
High
52
Bit 2 fixedfreq.Array
High
53
Bit 3 fixedfreq.Array
High
54
Bit 4 fixedfreq.Array
High
55
… 64
Reserved POSICON.
65
3-Wire-Direction
(closing switch to reverse
direction of rotation)
See functions {45, 46, 49}
0
1
Flank
66
… 70
Reserved
71
Motorpot.F+ and Save
“
Motor potentiometer function fre/
-
with automatic
saving
”. With this motor potentiometer function, a setpoint (sum)
is set via the digital inputs and is simultaneously saved. With
controller enabling R/L, this is then started up in the
corresponding enable rotation direction. The frequency is
retained on change of direction.
Simultaneous activation of the +/- function causes the
frequency setpoint to be set to zero.
The frequency setpoint value can also be displayed or set in the
operating value display (
P001 = 30
, actual setpoint MP-S) or in
P718
and can be pre-set in the "Ready to switch-on" operating
mode.
A set minimum frequency
P104
is still effective. Other setpoint
values, e.g. analogue or fixed frequencies, can be added or
subtracted.
Adjustment of the frequency setpoint value is performed with
the ramps from
P102 / 103
.
High
72
Motorpot.F- and Save
High
73
2)
Inhibit right+quick
Same as setting {31}, but coupled to the “Quick Stop” function.
Low
74
2)
Inhibit left + quick
Same as setting {32}, but coupled to the “Quick Stop” function.
Low
75
… 76
Reserved
77
… 78
Reserved POSICON.
79
Rotorpos. Ident
Precise knowledge of the rotor position is essential for PMSM
operation. Rotor position identification is performed if the
following conditions are met:
•
The frequency inverter is in the status “ready to switch-on”,
•
The rotor position is not known (see
P434
,
P481
, function{28}),
•
Function {2} is selected in
P336
.
0
1
Flank
80
PLC stop
The program execution of the internal PLC is stopped for as
long as the signal is present.
High
81
Frequency measurement
Input 3
The frequency measured via the analogue input (
P400 [-09]
) is
used as the setpoint (2 kHz to 22 kHz)
Note:
Only functions with DI3
Pulses
82
Duty measurement Input 3 The duty cycle (20 % … 80 % at 2 kHz) measured via the
analogue input (
P400 [-09]
) is used as the setpoint.
Note:
Only functions with DI3
Pulses
1)
If neither of the digital inputs is programmed for left or right enable, actuation of a fixed frequency or jog
frequency enables the frequency inverter. The rotation field direction depends on the sign of the setpoint.
2)
Also effective for Bus control (e.g. RS232, RS485, CANbus, CANopen, …)
3)
Function cannot be selected via BusIO In Bits
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...