5. PARAMETERS
5 - 12
5.2 Detailed list of parameters
POINT
Set a value to each "x" in the "Setting digit" columns.
5.2.1 Basic setting parameters ([Pr. PA_ _ ])
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
Control
mode
P S T
PA01
*STY
Operation
mode
_ _ _ x Control mode selection
Select a control mode.
0: Position control mode
1: Position control mode and speed control mode
2: Speed control mode
3: Speed control mode and torque control mode
4: Torque control mode
5: Torque control mode and position control mode
0h
_ _ x _ Operation mode selection
0: Standard control mode
1: Fully closed loop control mode
4: Linear servo motor control mode
6: DD motor control mode
Setting other than above will trigger [AL. 37 Parameter error]. The linear servo
system, direct drive servo system and fully closed loop system are available for the
MR-J4-_A_(-RJ) servo amplifiers of which software version is A5 or later.
For MR-J4-03A6 servo amplifiers, this digit cannot be used when a setting value
other than the initial value is set.
0h
_ x _ _ For manufacturer setting
0h
x _ _ _
1h
Содержание MR-J4
Страница 9: ...A 8 MEMO ...
Страница 19: ...10 MEMO ...
Страница 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Страница 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Страница 199: ...4 STARTUP 4 44 MEMO ...
Страница 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Страница 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Страница 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Страница 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Страница 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Страница 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Страница 763: ...APPENDIX App 38 ...
Страница 789: ...MEMO ...
Страница 793: ......