18. MR-J4-03A6 SERVO AMPLIFIER
18 - 13
(2) Installation of two or more servo amplifiers
POINT
You can install MR-J4-03A6 servo amplifiers without clearances between them.
When closely mounting the servo amplifiers, operate them at the ambient
temperatures of 0
˚
C to 45
˚
C.
Leave a large clearance between the top of the servo amplifier and the cabinet walls, and install a
cooling fan to prevent the internal temperature of the cabinet from exceeding the environment.
When mounting the servo amplifiers closely, leave a clearance of 1 mm between the adjacent servo
amplifiers in consideration of mounting tolerances. In this case, operate at the ambient temperatures 0
˚
C to 45
˚
C.
100 mm or more
10 mm or more
30 mm
or more
30 mm
or more
40 mm
or more
Cabinet
Top
Bottom
100 mm or more
1 mm
30 mm
or more
40 mm
or more
Cabinet
1 mm
Leaving clearance
Mounting closely