18. MR-J4-03A6 SERVO AMPLIFIER
18 - 71
18.5.9 Output signal (DO) forced output
POINT
When the servo system is used in a vertical lift application, turning on MBR
(Electromagnetic brake interlock) by the DO forced output after assigning it to
connector CN1 will release the electromagnetic brake, causing a drop. Take
drop preventive measures on the machine side.
Output signals can be switched on/off forcibly independently of the servo status. Use this function for
checking output signal wiring, etc. This operation must be performed in the servo off state by turning off SON
(Servo-on).
The following shows the display at power-on. Use the "MODE" button to display the diagnostic screen.
……
……
……
……
Switch on/off the signal below the lit segment.
Indicates on/off of output signal. Definitions of
on/off are the same as those for the external I/O
signals. (Light on: on, light off: off)
Press the "UP" button three times.
Press the "SET" button for 2 s or more.
CN1
33
CN1
48
CN1
22
CN1
25
CN1
23
CN1
49
Press the "MODE" button once.
Press the "UP" button once.
CN1-24 switches on.
(Between CN1-24 and DOCOM are connected.)
The lit LED moves to the upper LED of CN1-24.
Press the "DOWN" button once.
CN1-24 switches off.
Press the "SET" button for 2 s or more.
Always lit
CN1
24
……
Содержание MR-J4
Страница 9: ...A 8 MEMO ...
Страница 19: ...10 MEMO ...
Страница 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Страница 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Страница 199: ...4 STARTUP 4 44 MEMO ...
Страница 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Страница 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Страница 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Страница 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Страница 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Страница 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Страница 763: ...APPENDIX App 38 ...
Страница 789: ...MEMO ...
Страница 793: ......