APPENDIX
App. - 6
(b) Selection example of MCCB and fuse
Use T class fuses or molded-case circuit breaker (UL 489 Listed MCCB) as the following table. The
T class fuses and molded-case circuit breakers in the table are selected examples based on rated
I/O of the servo amplifiers. When you select a smaller capacity servo motor to connect it to the servo
amplifier, you can also use smaller capacity T class fuses or molded-case circuit breaker than ones
in the table. For selecting ones other than Class T fuses and molded-case circuit breakers below,
refer to section 11.10.
Power supply specification
Circuit protector
MR-J4-03A6 MR-J4W2-0303B6
Main circuit power supply (48 V DC)
CP30-BA 1P 1-M 3A
CP30-BA 1P 1-M 5A
Main circuit power supply (24 V DC)
CP30-BA 1P 1-M 5A
CP30-BA 1P 1-M 10A
Servo amplifier (100 V class)
Molded-case circuit breaker (120 V AC)
Fuse (300 V)
MR-J4-10_1/MR-J4-20_1/MR-J4-40_1 NV50-SVFU-15A (50 A frame 15 A)
20 A
Servo amplifier (200 V class) (Note)
Molded-case circuit breaker (240 V AC)
Fuse (300 V)
MR-J4-10_/MR-J4-20_/MR-J4-40_/MR-J4-60_ (T)/MR-J4-70_ (T)/
MR-J4W2-22B (T)
NF50-SVFU-5A (50 A frame 5 A)
10 A
MR-J4-60_ (S) /MR-J4-70_ (S) /MR-J4-100_/MR-J4W2-22B (S) /
MR-J4W2-44B (T)/MR-J4W2-77B (T)/MR-J4W3-222B/
MR-J4W3-444B (T)
NF50-SVFU-10A (50 A frame 10 A)
15 A
MR-J4-200_/MR-J4W2-44B (S) /MR-J4W2-1010B
NF50-SVFU-15A (50 A frame 15 A)
30 A
MR-J4-350_/MR-J4W2-77B (S) /MR-J4W3-444B (S)
NF50-SVFU-20A (50 A frame 20 A)
40 A
MR-J4-500_
NF50-SVFU-30A (50 A frame 30 A)
60 A
MR-J4-700_
NF50-SVFU-40A (50 A frame 40 A)
80 A
MR-J4-11K_
NF100-CVFU-60A (100 A frame 60 A)
125 A
MR-J4-15K_
NF100-CVFU-80A (100 A frame 80 A)
150 A
MR-J4-22K_
NF225-CWU-125A (225 A frame 125 A)
300 A
Note. "(S)" means 1-phase 200 V AC power input and "(T)" means 3-phase 200 V AC power input in the table.
Servo amplifier (400 V class)
Molded-case circuit breaker (480 V AC)
Fuse (600 V)
MR-J4-60_4/MR-J4-100_4
NF100-HRU-5A (100 A frame 5 A)
10 A
MR-J4-200_4
NF100-HRU-10A (100 A frame 10 A)
15 A
MR-J4-350_4
NF100-HRU-10A (100 A frame 10 A)
20 A
MR-J4-500_4
NF100-HRU-15A (100 A frame 15 A)
30 A
MR-J4-700_4
NF100-HRU-20A (100 A frame 20 A)
40 A
MR-J4-11K_4
NF100-HRU-30A (100 A frame 30 A)
60 A
MR-J4-15K_4
NF100-HRU-40A (100 A frame 40 A)
80 A
MR-J4-22K_4
NF100-HRU-60A (100 A frame 60 A)
125 A
(c) Power supply
This servo amplifier can be supplied from star-connected supply with grounded neutral point of
overvoltage category III (overvoltage category II for MR-J4-03A6 and MR-J4W2-0303B6) set forth in
IEC/EN 60664-1. However, when you use the neutral point for single phase supply, a reinforced
insulating transformer is required in the power input section. For the interface power supply, use an
external 24 V DC power supply with reinforced insulation on I/O terminals.
In case of MR-J4-03A6 and MR-J4W2-0303B6, use DC power supplies of reinforced insulation type
to main circuit, control circuit, and UL listed (recognized) 48 V DC/24 V DC power supplies which
can generate more than 1.2 A/2.4 A per axis.
Содержание MR-J4
Страница 9: ...A 8 MEMO ...
Страница 19: ...10 MEMO ...
Страница 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Страница 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Страница 199: ...4 STARTUP 4 44 MEMO ...
Страница 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Страница 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Страница 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Страница 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Страница 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Страница 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Страница 763: ...APPENDIX App 38 ...
Страница 789: ...MEMO ...
Страница 793: ......