12. ABSOLUTE POSITION DETECTION SYSTEM
12 - 29
(d) At the time of forced stop reset
210 ms after the forced stop is deactivated, the base circuit turns on, and RD turns on further 5 ms
after that, turns on. Always get the current position data using RD as the trigger before the position
command is issued.
1) When power is switched on in a forced stop status
OFF
210 ms
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
5 ms
During this period, get absolute position data.
Current position change
Power
supply
Base circuit
Pulse train command
Current position
Absolute position
data receive
Absolute position data
command transmission
SON
EM2
RD
Absolute position
data
2) When a forced stop is activated during servo on
95 ms
ON
OFF
ON
OFF
ON
OFF
ON
OFF
5 ms
Pulse train command
Current position
Absolute position
data receive
Absolute position data
command transmission
Current position change
During this period, get absolute position data.
Base circuit
SON
EM2
RD
Absolute position
data
Содержание MR-J4
Страница 9: ...A 8 MEMO ...
Страница 19: ...10 MEMO ...
Страница 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Страница 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Страница 199: ...4 STARTUP 4 44 MEMO ...
Страница 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Страница 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Страница 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Страница 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Страница 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Страница 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Страница 763: ...APPENDIX App 38 ...
Страница 789: ...MEMO ...
Страница 793: ......