MDS-E/EH Series Instruction Manual
5 Servo Adjustment
259
IB-1501229-F
< Initial implementation >
When using OMR-FF function, perform the following adjustment items beforehand. The adjustment for OMR-
FF function does not operate correctly if the following items are not performed.
< Setting method >
(1) Confirm that OMR-FF function is invalid.
#2139 : omrff_off= "1"
#2313 : SV113(SSF8)/bit0 = "0"
(2) Set the standard parameters for the motor to be used.
(3) Enable SHG control.
Set #2203 : SV003(PGN1) to the standard setting, "33".
Set #2204 : SV004(PGN2) to "88".
Set #2257 : SV057(SHGC) to "198".
Set #2208 : SV008(VIA) to "1900".
(4) Adjust the speed loop gain. Adjust so that VGN1 is an appropriate value (the result of frequency response
measurement on NC Analyzer is "Gain Margin > 8dB / Phase Margin > 30deg").
-> For the adjustment method, refer to the section "6.1.2 (3) Adjusting the speed loop parameter".
(5) Confirm that acceleration/deceleration operation can be executed with no alarm.
(6) Set SV035(SSF4)/bitF(clt) to "1" and repeat acceleration/deceleration several times. Check the estimated
inertia value on the NC monitor screen and set the displayed value to SV037(JL).
(7) Set SV003(PGN1) .
Check "Cross Freq (Hz)" with frequency response measurement on NC Analyzer.
SV003(PGN1) = "Cross Freq (Hz)" × 2
π
/ 4
(Example 1) Measurement value Cross Freq : 100Hz
Since 100(Hz) × 2
π
/ 4
≒
157, set SV003(PGN1) to 157.
* The value of SV003(PGN1) must be set for each axis to be used.
【
#2139
】
omrff_off OMR-FF invalid
Select whether to enable or temporarily disable the OMR-FF control when OMR-FF is valid.
0 : OMR-FF function is applied if OMR-FF function is enabled.
1 : OMR-FF function is temporarily disabled and conventional feed forward control is applied if
OMR-FF function is enabled.
Содержание MDS-E
Страница 1: ......
Страница 3: ......
Страница 15: ......
Страница 17: ......
Страница 19: ......
Страница 21: ......
Страница 31: ......
Страница 32: ...1 IB 1501229 F 1 Installation ...
Страница 76: ...45 IB 1501229 F 2 Wiring and Connection ...
Страница 132: ...101 IB 1501229 F 3 Safety Function ...
Страница 142: ...111 IB 1501229 F 4 Setup ...
Страница 277: ...MDS E EH Series Instruction Manual 4 Setup 246 IB 1501229 F ...
Страница 278: ...247 IB 1501229 F 5 Servo Adjustment ...
Страница 351: ...MDS E EH Series Instruction Manual 5 Servo Adjustment 320 IB 1501229 F ...
Страница 352: ...321 IB 1501229 F 6 Spindle Adjustment ...
Страница 404: ...373 IB 1501229 F 7 Troubleshooting ...
Страница 455: ...MDS E EH Series Instruction Manual 7 Troubleshooting 424 IB 1501229 F ...
Страница 456: ...425 IB 1501229 F 8 Maintenance ...
Страница 475: ...MDS E EH Series Instruction Manual 8 Maintenance 444 IB 1501229 F ...
Страница 476: ...445 IB 1501229 F 9 Power Backup System ...
Страница 494: ...463 IB 1501229 F 10 Appx 1 Cable and Connector Assembly ...
Страница 504: ...473 IB 1501229 F 11 Appx 2 D A Output Specifications for Drive Unit ...
Страница 513: ...MDS E EH Series Instruction Manual 11 Appx 2 D A Output Specifications for Drive Unit 482 IB 1501229 F ...
Страница 514: ...483 IB 1501229 F 12 Appx 3 Protection Function ...
Страница 523: ...MDS E EH Series Instruction Manual 12 Appx 3 Protection Function 492 IB 1501229 F ...
Страница 524: ...493 IB 1501229 F 13 Appx 4 Compliance to EC Directives ...
Страница 528: ...497 IB 1501229 F 14 Appx 5 EMC Installation Guidelines ...
Страница 540: ...509 IB 1501229 F 15 Appx 6 Higher Harmonic Suppression Measure Guidelines ...
Страница 545: ...MDS E EH Series Instruction Manual 15 Appx 6 Higher Harmonic Suppression Measure Guidelines 514 IB 1501229 F ...
Страница 550: ......
Страница 554: ......