10 User PLC Alarms (U)
115
IB-1501279-H
Details
Execution project illegal (at the PLC system startup)
Multi-project parameter setting is illegal (due to the following reasons).
The value outside the setting range (ON/OFF) was detected.
All execution projects are OFF.
Remedy
(1) The multi-project parameter (execution project) setting is illegal. Set the multi-project parameter again.
(2) If (1) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsubishi.
Details
Project execution order illegal (at the PLC system startup)
Multi-project parameter setting is illegal (due to the following reasons).
The value outside the setting range (1 to 6) was detected.
The redundant project execution order number was detected.
Remedy
(1) The multi-project parameter (project execution order) setting is illegal. Set the multi-project parameter
again.
(2) If (1) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsubishi.
Details
Parameter setting illegal for the number of common device points (at PLC system startup)
Multi-project parameter setting is illegal (due to the following reasons).
The value outside the setting range (0 to the minimum number of points in all projects) was detected.
It was detected that the number of points was not a multiple of 16.
Remedy
(1) Check the presence of the expansion project additional specification and reconsider the setting range.
(2) The multi-project parameter setting is illegal. Set the multi-project parameter again.
(3) If (1) or (2) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsub-
ishi.
Details
Parameter setting illegal for number of device points (at PLC system startup)
The parameter setting for the number of device points is illegal (due to the following reasons).
The total number of points in one project 29K or more was set.
The illegal value (-1 point or less, or 61441 points or more) for the number of device points was detected.
It was detected that the number of device points was not a multiple of 16.
The number outside the usable number of device points in whole projects was detected.
Remedy
(1) The parameter setting for the number of device points is illegal. Set the parameter of the number of device
points again and reboot the system.
(2) If (1) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsubishi.
Details
Caution; Ladder program writing during RUN is disabled (In independent program method)
With RUN write ON, sequence program is operated in independent program method. Run write is not available
with this condition.
Remedy
The ladder program writing (RUN write) can not be used in independent program method.
Disable RUN write, or change the method into multi-program one.
U10
Illegal PLC
0x550*
-
U10
Illegal PLC
0x560*
-
U10
Illegal PLC
0x570*
-
U10
Illegal PLC
0x580*.yy
-
U10
Illegal PLC
0x700*.yy
-
Содержание C80 Series
Страница 1: ......
Страница 7: ......
Страница 11: ......
Страница 13: ......
Страница 15: ......
Страница 18: ...1 IB 1501279 H Alarm ...
Страница 19: ...M800 M80 E80 C80 Series Alarm Parameter Manual 2 IB 1501279 H ...
Страница 20: ...1 3 IB 1501279 H Operation Errors M ...
Страница 54: ...2 37 IB 1501279 H Stop Codes T ...
Страница 62: ...3 45 IB 1501279 H Servo Spindle Alarms S ...
Страница 81: ...M800 M80 E80 C80 Series Alarm Parameter Manual 3 Servo Spindle Alarms S 64 IB 1501279 H ...
Страница 82: ...4 65 IB 1501279 H MCP Alarms Y ...
Страница 98: ...5 81 IB 1501279 H System Alarms Z ...
Страница 111: ...M800 M80 E80 C80 Series Alarm Parameter Manual 5 System Alarms Z 94 IB 1501279 H ...
Страница 112: ...6 95 IB 1501279 H Absolute Position Detection System Alarms Z7 ...
Страница 117: ...M800 M80 E80 C80 Series Alarm Parameter Manual 6 Absolute Position Detection System Alarms Z7 100 IB 1501279 H ...
Страница 118: ...7 101 IB 1501279 H Distance coded Reference Scale Errors Z8 ...
Страница 120: ...8 103 IB 1501279 H Emergency Stop Alarms EMG ...
Страница 124: ...9 107 IB 1501279 H Computer Link Errors L ...
Страница 126: ...10 109 IB 1501279 H User PLC Alarms U ...
Страница 136: ...11 119 IB 1501279 H Network Service Errors N ...
Страница 139: ...M800 M80 E80 C80 Series Alarm Parameter Manual 11 Network Service Errors N 122 IB 1501279 H ...
Страница 140: ...12 123 IB 1501279 H Program Errors P ...
Страница 178: ...13 161 IB 1501279 H Smart Safety Observation Alarm V ...
Страница 192: ...14 175 IB 1501279 H Multi CPU Errors A C80 ...
Страница 215: ...M800 M80 E80 C80 Series Alarm Parameter Manual 14 Multi CPU Errors A C80 198 IB 1501279 H ...
Страница 216: ...199 IB 1501279 H Parameter ...
Страница 217: ...M800 M80 E80 C80 Series Alarm Parameter Manual 200 IB 1501279 H ...
Страница 218: ...15 201 IB 1501279 H User Parameters ...
Страница 359: ...M800 M80 E80 C80 Series Alarm Parameter Manual 15 User Parameters 342 IB 1501279 H ...
Страница 360: ...16 343 IB 1501279 H Machine Parameters ...
Страница 748: ......