Chapter 7. Usage of Various Functions
7-40
6) Error code list
(1) PID7AT
Error
Code
Description
Countermeasure
H01
Auto tuning parameter setting
error
Set the auto tuning parameters within the range.
H02
Auto tuning direction setting
error
Set the direction forward or reverse.
H03
Scan time setting range error
Set scan time in available setting range (1~100).
H04
SV setting range error
Set SV in available setting range (0~4000).
H05
PV setting range error
Set PV setting address in available range (%MW0~%MW5119) or
check whether PV is out of range (0~4000).
H06
PRC auto tuning execution error
PV is bigger than 80% of SV(or less than 120% of SV in reverse
operation) at the starting point of auto tuning.
H07
LOOP duplication error
Do not execute the auto tuning using the parameters used in other
FB.
H08
LOOP number error
Set the loop number correctly (0~7).
(2) PID7CAL
Error
Code
Description
Countermeasure
H01
Mode command setting error
Set the mode command P(+PWM), PI(+PWM) or PID(+PWM) only.
Do not set I, D, ID or PD.
H03
Scan time setting range error
Set scan time to available setting range (1~100).
H04
Manual operation range error
Set manual operation value to available setting range.
H05
Output limit value error(Min.)
Set minimum output limit value to available setting.
H06
Output limit value error(Max.)
Set maximum output limit value to available setting.
H07
Max./Min. output setting error
Set the Min. value less than the Max. value.
H08
P gain setting error
Set P gain period to available setting range.
H09
I time setting error
Set I time period to available setting range.
H0A
D time setting error
Set D time period to available setting range.
H0B
Bias setting error
Set Bias to available setting range.
H0C
PV setting range error
Set P gain period to available setting range (%MW0~%MW5119), or
check whether PV is in the range of 0~4000.
H0D
SV setting range error
Set SV to available setting range.
H0E
SV Ramp setting error
Set SV Ramp to available setting range.
H0F
Delta MV setting error
Set Delta MV to available setting range.
H10
PID algorithm setting error
Check PID algorithm setting.
H11
Operation mode setting error
Available operation mode is 0 or 1.
Содержание GLOFA G7M-DR20U
Страница 28: ...Chapter 4 Names of Parts 4 3 2 G7M DRT60U N 3 G7M DT60U N 4 G7M DT60U P...
Страница 29: ...Chapter 4 Names of Parts 4 4 5 G7M DR60U DC 6 G7M DRT60U N DC 7 G7M DT60U N DC...
Страница 30: ...Chapter 4 Names of Parts 4 5 8 G7M DT60U P DC 4 1 2 40 point main unit 1 G7M DR40U 2 G7M DRT40U N...
Страница 31: ...Chapter 4 Names of Parts 4 6 3 G7M DT40U N 4 G7M DT40U P 5 G7M DR40U DC...
Страница 32: ...Chapter 4 Names of Parts 4 7 6 G7M DRT40U N DC 7 G7M DT40U N DC 8 G7M DT40U P DC...
Страница 33: ...Chapter 4 Names of Parts 4 8 4 1 3 30 point main unit 1 G7M DR30U 2 G7M DRT30U N 3 G7M DT30U N...
Страница 34: ...Chapter 4 Names of Parts 4 9 4 G7M DT30U P 5 G7M DR30U DC 6 G7M DRT30U N DC...
Страница 35: ...Chapter 4 Names of Parts 4 10 7 G7M DT30U N DC 8 G7M DT30U P DC 4 1 4 20 point main unit 1 G7M DR20U...
Страница 36: ...Chapter 4 Names of Parts 4 11 2 G7M DRT20U N 3 G7M DT20U N 4 G7M DT20U P...
Страница 37: ...Chapter 4 Names of Parts 4 12 5 G7M DR20U DC 6 G7M DRT20U N DC 7 G7M DT20U N DC...
Страница 38: ...Chapter 4 Names of Parts 4 13 8 G7M DT20U P DC...
Страница 159: ...Chapter 7 Usage of Various Functions 7 52 c Program...
Страница 183: ...Chapter 7 Usage of Various Functions 7 76 c Program...
Страница 253: ...Chapter 8 Communication Functions 8 27 b When uses Ch 1 Built in RS 485...
Страница 355: ...Appendix 1 System Definitions App1 8 5 PID parameters 1 PID Auto Tuning Parameter 2 PID Parameter...
Страница 356: ...Appendix 1 System Definitions App1 9 6 Position Parameter...
Страница 357: ...Appendix 1 System Definitions App1 10 7 High Speed Counter Parameter...