Chapter 10. Maintenance
10-2
10.3 Periodic Inspection
Check the following items once or twice every six months, and perform the needed corrective actions.
Check Items
Checking Methods
Judgment
Countermeasure
Ambient
temperature
0 ~ 55
°
C
Ambient Humidity
5 ~ 95%RH
Ambient
Environment
Ambience
-. Measure with thermometer
and hygrometer
-. measure corrosive gas
There should be no
corrosive gases
Adjust to general standard
(Internal environmental standard
of control section)
Looseness,
Ingress
The module should be move
the unit
The module should be
mounted securely.
PLC
Conditions
dust or foreign
material
Visual check
No dust or foreign material
Retighten screws
Loose terminal
screws
Re-tighten screws
Screws should not be loose Retighten
Distance between
terminals
Visual check
Proper clearance
Correct
Co
nnec
tin
g
co
nd
itions
Loose connectors Visual check
Connectors should not be
loose.
Retighten connector mounting
Screws
Line voltage check
Measure voltage between
input terminals
*85 ~ 264V AC
*10.2 ~ 28.8V DC
Change supply power
Fuse
Visual check
No melting disconnection
If fuse melting disconnection,
change the fuse periodically
because a surge current can
cause heat
Содержание GLOFA G7M-DR20U
Страница 28: ...Chapter 4 Names of Parts 4 3 2 G7M DRT60U N 3 G7M DT60U N 4 G7M DT60U P...
Страница 29: ...Chapter 4 Names of Parts 4 4 5 G7M DR60U DC 6 G7M DRT60U N DC 7 G7M DT60U N DC...
Страница 30: ...Chapter 4 Names of Parts 4 5 8 G7M DT60U P DC 4 1 2 40 point main unit 1 G7M DR40U 2 G7M DRT40U N...
Страница 31: ...Chapter 4 Names of Parts 4 6 3 G7M DT40U N 4 G7M DT40U P 5 G7M DR40U DC...
Страница 32: ...Chapter 4 Names of Parts 4 7 6 G7M DRT40U N DC 7 G7M DT40U N DC 8 G7M DT40U P DC...
Страница 33: ...Chapter 4 Names of Parts 4 8 4 1 3 30 point main unit 1 G7M DR30U 2 G7M DRT30U N 3 G7M DT30U N...
Страница 34: ...Chapter 4 Names of Parts 4 9 4 G7M DT30U P 5 G7M DR30U DC 6 G7M DRT30U N DC...
Страница 35: ...Chapter 4 Names of Parts 4 10 7 G7M DT30U N DC 8 G7M DT30U P DC 4 1 4 20 point main unit 1 G7M DR20U...
Страница 36: ...Chapter 4 Names of Parts 4 11 2 G7M DRT20U N 3 G7M DT20U N 4 G7M DT20U P...
Страница 37: ...Chapter 4 Names of Parts 4 12 5 G7M DR20U DC 6 G7M DRT20U N DC 7 G7M DT20U N DC...
Страница 38: ...Chapter 4 Names of Parts 4 13 8 G7M DT20U P DC...
Страница 159: ...Chapter 7 Usage of Various Functions 7 52 c Program...
Страница 183: ...Chapter 7 Usage of Various Functions 7 76 c Program...
Страница 253: ...Chapter 8 Communication Functions 8 27 b When uses Ch 1 Built in RS 485...
Страница 355: ...Appendix 1 System Definitions App1 8 5 PID parameters 1 PID Auto Tuning Parameter 2 PID Parameter...
Страница 356: ...Appendix 1 System Definitions App1 9 6 Position Parameter...
Страница 357: ...Appendix 1 System Definitions App1 10 7 High Speed Counter Parameter...