![LS Industrial Systems GLOFA G7M-DR20U Скачать руководство пользователя страница 263](http://html1.mh-extra.com/html/ls-industrial-systems/glofa-g7m-dr20u/glofa-g7m-dr20u_user-manual_1943826263.webp)
Chapter 8. Communication Functions
8-37
8.1.8 Error codes
Error code
Error type
Error condition and causes
Treatment
H0001 PLC system error Interface with PLC is impossible.
Turn Off/On the power
H0011 Data error
Errors occurred when exchanging ASCII data to
numbers.
Check if other letters than capitals/small letters,
numbers, and (‘%’,’_’,’.’) in device and data,
correct and execute again
H0021 Command error
Set a wrong device memory that is to use
commands other than w(W), r(R), x(X), y(Y), s(S)
Check the commands
H0031 Command type error
Wrong command type that is to use characters
like wSS, wSB using other letters from “SS” or “SB”
Check the command type
H1132 Device memory error A memory device other than m(M),q(Q),I(I) is set.
Check the device type
H1232 Data size error
The number of data is 0 or longer than 128
bytes.
Correct data length
(If the data type is byte, the number of data
must be from 1~128)
H2432 Data type error
When characters other than x(X), b(B),w(W),d(D)
are used.
When b(B), d(D) are used.
Ex) Use commands like %db or %dd.
Check the data type and execute again.
H7132 Device request
Format error
When omit %
When omit ‘.’ at QX command
Check the data type and execute again
H2232 Exceeded area error
When the assigned area is exceed
Ex 1) %QX0.0.64
Æ
exceed assigned area
%MB0.0.8
Æ
exceed assigned area
Ex 2) The address is not in decimal value such
as %MX00A, %MB00A
Ex 3) When the M area size is set as 2 K bytes
in GMWIN, but exceeds over 2 K bytes
like %MB400.
Correct the size within the assigned area and
execute again.
H0190 Monitor execution
error
Exceeding limit of register No.
Correct the monitor register no. not to go over
than 9 and reset
H0290 Monitor register error Exceeding limit of register No.
Correct the monitor register no. not to go over
than 9 and reset
H6001 Syntax error
When use commands that aren’t supported. Ex1)
When use device like %MX100, %QX0.0.0 in RSB
command
- Be familiar with the manual
- Check if the system stopped
- Reset
H6010 Syntax error
OVER-RUN, FRAME error
Be familiar with the manual
H6020 Syntax error
TIME_OUT error
Confirm the setting of the RS-232C
communication ports. Turn the power off and on
to restart.
H6030 Syntax error
Syntax error in commands
Check if each sends frame has ENQ, EOT.
H6040 Syntax error
When a FRAME text exceeds over 256 bytes
Correct the send frame not to go over 256 bytes.
H6050 Syntax error
BCC error
Check if BCC is right.
Содержание GLOFA G7M-DR20U
Страница 28: ...Chapter 4 Names of Parts 4 3 2 G7M DRT60U N 3 G7M DT60U N 4 G7M DT60U P...
Страница 29: ...Chapter 4 Names of Parts 4 4 5 G7M DR60U DC 6 G7M DRT60U N DC 7 G7M DT60U N DC...
Страница 30: ...Chapter 4 Names of Parts 4 5 8 G7M DT60U P DC 4 1 2 40 point main unit 1 G7M DR40U 2 G7M DRT40U N...
Страница 31: ...Chapter 4 Names of Parts 4 6 3 G7M DT40U N 4 G7M DT40U P 5 G7M DR40U DC...
Страница 32: ...Chapter 4 Names of Parts 4 7 6 G7M DRT40U N DC 7 G7M DT40U N DC 8 G7M DT40U P DC...
Страница 33: ...Chapter 4 Names of Parts 4 8 4 1 3 30 point main unit 1 G7M DR30U 2 G7M DRT30U N 3 G7M DT30U N...
Страница 34: ...Chapter 4 Names of Parts 4 9 4 G7M DT30U P 5 G7M DR30U DC 6 G7M DRT30U N DC...
Страница 35: ...Chapter 4 Names of Parts 4 10 7 G7M DT30U N DC 8 G7M DT30U P DC 4 1 4 20 point main unit 1 G7M DR20U...
Страница 36: ...Chapter 4 Names of Parts 4 11 2 G7M DRT20U N 3 G7M DT20U N 4 G7M DT20U P...
Страница 37: ...Chapter 4 Names of Parts 4 12 5 G7M DR20U DC 6 G7M DRT20U N DC 7 G7M DT20U N DC...
Страница 38: ...Chapter 4 Names of Parts 4 13 8 G7M DT20U P DC...
Страница 159: ...Chapter 7 Usage of Various Functions 7 52 c Program...
Страница 183: ...Chapter 7 Usage of Various Functions 7 76 c Program...
Страница 253: ...Chapter 8 Communication Functions 8 27 b When uses Ch 1 Built in RS 485...
Страница 355: ...Appendix 1 System Definitions App1 8 5 PID parameters 1 PID Auto Tuning Parameter 2 PID Parameter...
Страница 356: ...Appendix 1 System Definitions App1 9 6 Position Parameter...
Страница 357: ...Appendix 1 System Definitions App1 10 7 High Speed Counter Parameter...