Installation, Maintenance, and Repair Manual

 

Series LF007

Double Check Valve Assembly

2½" – 3"

NOTICE

For Australia and New Zealand, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow 

preventer.
Watts product specifications in U.S. customary units and metric 

are approximate and are provided for reference only. For precise 

measurements, contact Watts Technical Service. Watts reserves 

the right to change or modify product design, construction, speci-

fications, or materials without prior notice and without incurring 

any obligation to make such changes and modifications on Watts 

products previously or subsequently sold.

RP/IS-LF007L

Testing

For field testing procedure, refer to the Watts installation sheets  

IS-TK-DL, IS-TK-9A, IS-TK-99E and IS-TK-99D at  

www.watts.com.
For technical assistance, contact your local Watts representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Local building or plumbing codes may require modifications 

to the information provided. You are required to consult the 

local building and plumbing codes prior to installation. If the 

information provided here is not consistent with local building 

or plumbing codes, the local codes should be followed. 

This product must be installed by a licensed contractor in 

accordance with local codes and ordinances.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product 

must be tested periodically in compliance with local codes, but 

at least once per year or more as service conditions warrant. 

All products must be retested once maintenance has been 

performed. Corrosive water conditions and/or unauthorized 

adjustments or repair could render the product ineffective for the 

service intended. Regular checking and cleaning of the product’s 

internal and external components helps assure maximum life and 

proper product function. 

WARNING

!

Series LF007 large-diameter backflow preventer is designed for 

installation at referenced cross-connections to prevent the backflow 

of polluted water into the potable water supply. Series LF007 Model IOT 

includes factory-installed pressure sensors. 

LF007-NRS-IOT

NOTICE

Use of integrated pressure sensors and monitoring connection 

kit with Model IOT does not remove the need to comply with all 

required instructions, codes, and regulations related to installation, 

operation, and maintenance of the backflow preventer.
Watts is not responsible for data transmission failures due to  

connectivity issues, power outages, or improper installation.

NOTICE

An add-on monitoring connection kit is required to collect psi 

measurements from the integrated pressure sensors. Without the 

connection kit, the pressure sensors are passive components 

that do not communicate with any other device. For BMS only. 

(The connection kit and pressure sensors are also available for 

existing installations. For ordering details, see “Add-on Monitoring 

Connection Kits.”

Содержание LF007 Series

Страница 1: ...lled by a licensed contractor in accordance with local codes and ordinances WARNING Need for Periodic Inspection Maintenance This product must be tested periodically in compliance with local codes but...

Страница 2: ...perated Certified testers of backflow assemblies must conduct this test The trim valves of the detector meter bypass line on assemblies so equipped should be shutoff during the confirming flow test Wh...

Страница 3: ...N Check valve fails to hold 1 0 PSID minimum Debris on check disc sealing surface Disassemble and clean Leaking gate valve Disassemble and clean or repair Damaged seat disc or seat O ring Disassemble...

Страница 4: ...rty which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions...

Страница 5: ...s et les ordonnances locaux AVERTISSEMENT Besoin d inspection et de maintenance p riodique Ce produit doit tre test p riodiquement conform ment aux codes locaux au moins une fois par an ou plus selon...

Страница 6: ...ement doivent effectuer ce test Les vannes de r glage de la conduite de d rivation du compteur du d tecteur sur les assemblages ainsi quip s doivent tre ferm es pendant l essai de confirmation du d bi...

Страница 7: ...ff rentielle de 1 0 lb po D bris sur la surface d tanch it du disque de contr le D montez et nettoyez Fuite du robinet vanne D montez et nettoyez ou r parez Disque de si ge ou joint torique de si ge e...

Страница 8: ...autres co ts r sultant des frais de main d uvre des retards du vandalisme de la n gligence de l encrassement caus s par des mati res trang res des dommages caus s par des conditions de l eau d favorab...

Страница 9: ...er instalado por un contratista autorizado de acuerdo con los reglamentos y ordenanzas locales ADVERTENCIA Se requiere inspecci n y mantenimiento peri dicos se debe probar peri dicamente este producto...

Страница 10: ...ficados de conjuntos de reflujo deben realizar esta prueba Las v lvulas de regulaci n de la l nea de derivaci n del medidor del detector en los conjuntos que est n equipados deben cerrarse durante la...

Страница 11: ...LUCI N La v lvula de retenci n no logra retener un m nimo de 1 0 psid 7 kPa Residuos en la superficie de sellado del disco de retenci n Desmontaje y limpieza V lvula de compuerta con fugas Desmontaje...

Страница 12: ...ctamente otros costos resultantes de cargos laborales demoras vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu micos o cualquie...

Отзывы: