Parameters [51]
Galaxy Flex Installer Manual
98
[51.57] Not used
Power Alarm [51.58]
Enable this parameter to allow the Bells, Strobe and Horn outputs to activate when there is
an a.c. failure and the system is set. The default is 0.
Part Tone [51.59]
Enable this parameter to change the setting tone for a part set. The new tone is on for 2
seconds and off for 0.1 seconds.
RF Address [51.60.1]
Use this option to specify the number of virtual RIO addresses available for wireless
detectors zones. Up to 24 addresses in total can be allocated with a limit of 3 addresses for
each RF Portal configured.
Each RIO address is displayed with
E
if enabled for wireless or
D
if disabled. To change the
status, press
ent
.
Select
0
to disable or
1
to enable the line/address. When disabling a RIO address you may
be prompted to remove or reassign programmed zones to another RIO address.
RF Fob PA [51.60.2]
Use this option to enable a user to program the Panic Alert function of a wireless keyfob.
Note:
In some locations, the Panic Alert function may not be permissible.
RF Supervision [51.60.3]
1=Silent Alarm
Stop supervision alarms from activating sounders when set.
2=Debounce
Extends the normal 2 hour delay for supervision by a further 24 hours.
RF Bat Delay [51.60.4]
Use this option to give a warning at the panel if an RF low battery is detected. An additional
option allows a delay to be programmed of up to 100 hours (default) before a signal of RF
BAT LOW is sent to the ARC.
RF Jam Delay [51.60.5]
This option allows the RF Portal to send an RF jam signal to the panel if it detects
interference for 30 seconds. If the interference is continuously present for five minutes
(default), the signal is transmitted to the central station. The programmable range is 0 to 30
minutes.
RF Stop Set [51.60.6]
Enable this option to prevent setting if all supervised devices have not signalled to the
receiver in the stop set period, prior to setting. The range is 0 to 250 minutes. The default is
20 minutes.