Program Outputs [53]
Galaxy Flex Installer Manual
130
27 Fire Delay (Latch)
This output is activated whenever a Fire zone is activated. Activation is delayed subject to
the
51.03=Abort Time
parameter. The Fire Delay output is not subject to the Re-arm
parameter. It latches on and remains active until a valid code (type 2 or above) is entered.
28 No Re-Arm (Latch)
This output is activated on a full alarm event during the set state, and is subject to the Bell
Delay parameter. The No Re-arm output is similar to the strobe output, but it stays on at the
end of the bell time, until unset.
29 Timer A (Reflex)
This output is controlled by the Timer-A option (refer to
Timers [65]
) and activates in
accordance with the programmed on and off times assigned to the function.
30 Timer B (Reflex)
This output is controlled by the Timer-B option (refer to
Timers [65]
) and activates in
accordance with the programmed on and off times assigned to the function.
Note:
If the Timer A or B
outputs are programmed as Latch mode, then they can only be
reset by a user code with access to all of the groups assigned to the relevant timer.
32 Zone Omit (Reflex)
This output is activated by
11=OMIT ZONES
or by
54=LINKS
, as soon as a zone is
omitted from the system. If the Output Mode attribute is assigned as:
Reflex (default), the output remains active until the zone is reinstated.
Latch, the output is reset on entry of a valid code.
34 Custom
A (Latch)
This output is activated whenever a Custom-A zone is activated.
35 Custom
B (Latch)
This output is activated whenever a Custom-B zone is activated.
37 Reset RQD (Latch)
This output is activated when a system, tamper or PA alarm occurs that needs to be reset.
Refer to
Parameters [51]
for details modifying the code levels assigned to the
06=System
Reset
,
07=Tamper Reset
and
22=PA Reset
parameters.
39 Valid Code (Reflex)
The Valid Code output is activated by the entry of any valid code. If the Output Mode
is
Reflex, the output remains active while the user is accessing the menu and setting and
unsetting the system. Once the menu is exited or the system sets or unsets, the output is
restored.