Access Control [69]
Galaxy Flex Installer Manual
188
A second group map is allocated to each MAX in order to facilitate this function. This
permits the existing door control features to be completely detached from the fire
escape
features.
The default setting for each MAX is all groups selected. Therefore, a system which is
unchanged from the default will open all MAX doors in response to any fire zone activation.
On selecting the Emergencies option, select the groups you want allocated to the MAX for
escape purposes and accept the programming by pressing the enter key. When a fire zone is
activated in any of the groups programmed, the door controlled by the MAX will be opened.
Security Nightlock [69.2.2.6.1]
Use this option to allocate a time schedule to define when access to the door will be blocked.
Up to 4 weekly time schedules can be programmed. Setting the schedule to 00 disables the
function.
Security Unlock Time [69.2.2.6.2]
Use this option to allocate a time schedule to define when the door will be unlocked to
provide unrestricted access. Up to 10 weekly time schedules can be programmed, depending
on model (see Table 1 on page 11). Setting the schedule to 00 disables the function.
Security Dual Mode [69.2.2.6.3]
Use this option enable dual authority via the assigned keypad. The options are:
0=Disabled
A card or a PIN is required to gain access.
1=Card and Card
Two cards are required to gain access.
2=Card and Pin
A card and a PIN from the same user are required to gain access.
Menu Recall [69.2.2.7]
Use this option to assign a card-held function to the reader. Users are then able to perform
card-held functions even if they do not have card-held privileges.
1=Menu Function
Depending on the level of access granted in
Menu Access [68]
, a
user can hold a card at a compatible reader for three seconds to
activate a single function selected from the available list. Assign a
double asterisk (
) to the function to make it not used.
2=Menu Mode
This determines whether a card held function can be used to access
the reader. There is one option which is
1=Card Held
.
2=Keypad
This assigns a specific keypad address to work in conjunction with a
MAX. This keypad is used to display the menu action assigned in
1=Menu Function
.
Note:
If a function is assigned to both the User Code and the Max/DCM reader, only the
function from the User Code will be started.