Galaxy Flex Installer Manual
Parameters [51]
97
0=Disable Exits
Exit type zones will only cause unconfirmed intruder alarms. They will
not contribute to the two activations required for a confirmed alarm.
1=Enable Exits
After the expiry of the entry delay, activation of an exit type zone will
be identical to an intruder zone.
Confirm Reduce Reset [51.55.3]
Use this option to allow user reset following an unconfirmed alarm.
0=Off
Full system reset is required for any intruder alarm.
1=On Unconfirmed
The system can be reset by a user if the alarm is unconfirmed.
If the alarm is classed as confirmed, a full system reset is required.
Timeout Confirm [51.55.4]
Use this option to define if an Entry Time-out alarm will contribute to a confirmed alarm
0=Disabled
Time-out will not contribute (PD6662: 2004)
1=Enabled
Time-out will contribute (PD6662: 2010)
HU Confirm [51.55.5]
Use this option to define if a confirmed Hold-up alarm condition should be generated from
two separate Panic or hold-up zone types.
0=Disabled
Confirmed Hold-up condition will not be generated
1=Enabled
Confirmed Hold-up condition will be generated
HU Time [51.55.6]
Use this option to define the maximum time window between two separate panic zone
activations to generate a confirmed hold-up event. (1-20 hours)
Output type 20 response [51.55.7]
Use this option to define what events the Standard Confirm output type (type 20) will
respond to.
0=Confirmed Intruder events only
1=Confirmed Intruser and Confirmed Hold-up and even ts
A separate output type is also available for confirmed hold-up events only (type 84)
Force Restore [51.56]
Use this option to select when intruder restore signals are transmitted.
1=Unset/Unconfirm
On unset or at the end of the confirmed time if the alarm is not
confirmed.
2=System Reset
Sent when the system is fully reset.