The Part attribute of the Keyswitch function defaults to 0 (disabled) and the standard
Keyswitch function full sets the system. To part set the system using the Keyswitch, enable
the Part attribute.
Note:
The operation of a Keyswitch zone can be extended to the setting and unsetting of
multiple groups by pressing
when assigning a group to the zone. Refer to the Star
Group Function.
The standard programming of the Keyswitch function requires a momentary change from
1 k
Ω
to 2 k
Ω
to both set and unset the system. If the Keyswitch connected has a latching
mechanism, press
when assigning the function. The display indicates
09=KEYSWITCH
has been assigned. The Keyswitch operation is as follows: 1 k
Ω
to 2 k
Ω
sets the system;
2 k
Ω
to 1 k
Ω
unsets the system.
The Keyswitch function can also be programmed to reset alarms (refer to
Keyswitch Level
[51.14]
). If the Keyswitch is assigned a sufficient type to reset the alarm condition, the alarm
is cancelled and immediately reset when the Keyswitch is used to unset the system
following an alarm activation.
Note:
The activated zones are not displayed on the keypad when a Keyswitch is used to
reset the alarm.
10 Secure Final
This zone has dual functionality:
When the system is setting, set or unsetting operation is identical to the Final zone
function.
When the system is unset operation is identical to the Security zone function.
Pressing
when programming a Secure Final zone doubles the entry time of the group.
Opening a Secure Final zone during the exit time is reported on the keypad as an open zone
and the entry/exit horns bleep rapidly to indicate that the zone is open.
The termination feature of a Secure Final zone can be extended to terminate the setting of
multiple groups by pressing
when assigning a group to the zone. Refer to the Star
Group Function.
11 Part Final
This zone has dual functionality:
When the system is full set operation is identical to the Final zone function.
When the system is part set operation is identical to the Intruder zone function.
Pressing
when programming a Part Final zone doubles the entry time of the group.
Opening a Part Final zone during the exit time is reported on the keypad as an open zone;
the entry/exit horns bleep rapidly to indicate that the zone is open.
12 Part Entry
This zone has dual functionality: