Galaxy Flex Installer Manual
Appendix G: Peripherals
239
Configuration
Note:
MAX
4
readers can only be configured into the system from engineer mode.
1.
Access engineer mode.
2.
Check that
Access Mode [69.1]
is enabled.
3.
Configure the reader as On-Line or Standalone using
MAX Address [69.2.1]
: 0=On-
Line, 1=Standalone (default).
4.
Press
ent
. The panel may prompt for the AB line (1 – 4) that is to be searched; select
the line and press
ent
. The panel searches for the MAX
4
with the highest address. New
MAX
4
readers are addressed as 8 (standalone) by default.
5.
Only if adding a new MAX
4
reader: On locating the MAX
4
address, the keypad
prompts for the OPERATING MODE of MAX
4
to be assigned: select 0=On-Line or
1=Standalone as required and press
ent
. When 0=On-Line mode is selected, the keypad
displays the current address of the MAX
4
and the range of valid addresses. Enter the
new MAX
4
address and press
ent
. The keypad indicates the old and new MAX
4
addresses and the status of the reprogramming.
Note:
We recommend addressing new readers with the lowest available number on
the line.
When reprogramming is complete the MAX
4
bleeps, the LEDs on the MAX
4
switch off
and the keypad display returns to 1=MAX Address.
6.
Enter your engineer code, and then press
esc
to exit from engineer mode. The message
1 MOD. ADDED -
esc
=CONTINUE
is displayed on the keypad and LED 2 on the
MAX
4
reader switches on. Press
esc
and the keypad returns to the unset banner.
If this message is not displayed, the MAX
4
reader is not communicating with the
control panel and has not been configured into the system (LED 2 does not switch on).
The online MAX
4
reader is now configured into the system.
Operating instructions
Opening the door without presenting a valid card activates a door forced alarm at the panel;
the buzzer sounds and LED 2 flashes until the door is closed.
Activating the egress switch allows the door to be opened without activating an alarm when
no card has been presented to the MAX
4
.
1.
Ensure that LED 3 is on and all other LEDs are off.
2.
Swipe the reader with a standard user or nightlock access user card. LED 3 switches off
and LED 2 switches on for the programmed Open Timeout.
3.
Open the door while the LED 2 is on and access the area.