Program Zones [52]
Galaxy Flex Installer Manual
118
This function is designed to permit a remote signal, for example REDCare’s Return Path
Signalling feature, to reset the system following an alarm condition.
40 Bell Fail
This zone type is for bells that have diagnostic capabilities and failure outputs. If activated,
it causes fault for any bell failure condition.
41 Intr Low
This zone type assigns a low priority to a zone in the event of an intruder alarm. The event is
logged as low priority in the event log.
42 Intr High
This zone type assigns a high priority to a zone in the event of an intruder alarm. The event
is logged as high priority in the event log.
43 PSU Fault
This zone type triggers a general fault output and logs a PSU fault in the event log. The fault
is signalled to the ARC as YP when using SIA format and 314 when using CID format.
44 Fault
This zone type triggers a general fault output and logs a fault in the event log. The fault is
signalled to the ARC as IA when using SIA format and 150 when using CID format.
45 Entry 2
This function initiates the unsetting procedure in the same way as an Entry Zone type 07,
but follows the alternate entry timer in parameter 51.78.
53 HU Cancel
This zone type cancels the HU monitor timer, set in parameter 51.85.1.