Galaxy Flex Installer Manual
Program Outputs [53]
133
82 Fire Reset (Pulse)
This output is used to reset latching fire sensors which require removal of power in order t
oreset them following activation. The negative power supply to the sensor should be wired
to the Fire Reset output. Following an activation the fire sensors can be reset by pressing the
and
B
buttons simultaneously on a keypad. Power will be removed from the sensors for
the duration of the pulse time programming for the output. During this time all fire zones on
the system will be ignored.
83 Confirmed Fire Alarm (Latch)
This output activates when a PIR picks up heat from a fire that has already been signalled by
a smoke detector. This second activation is used to confirm the fire alarm, and a confirm
message is sent to the ARC.
84 HU Confirm (Latch)
This output activates in response to a confirmed hold-up event – either when two separate
PA zones are activated within the HU confirm time window or a confirmed hold-up zone
type is activated. Check the Hold up confirm parameters
[51.55]