![Honeywell Galaxy Flex 100 V3 Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/honeywell/galaxy-flex-100-v3/galaxy-flex-100-v3_installer-manual_153326038.webp)
Multi-user access
Galaxy Flex Installer Manual
38
To exit from Engineer Mode:
1.
Return to the engineer banner.
2.
Enter your engineer code.
3.
Press
esc
.
Note:
If
esc
is pressed during the following system checks, the exit is aborted and the
system remains in engineering mode.
Before the normal banner is displayed the system performs these checks:
That there are no open zones or tampers. If there are tampers, they are displayed to
allow investigation. Open zones are not displayed.
That it is communicating with all of the attached modules. If any modules are
missing, the system prompts the engineer to press
to remove them. If the
engineer does not remove the missing modules, the
escape procedure is aborted.
That data bus communication is working. If communication with any module is
less than 100% successful a warning is provided.
That there are no power failures on the system, such as a failure of the a.c. or
battery.
Multi-user access
The system allows a maximum of 4 users to carry out tasks at the same time via separate
user interfaces.