Galaxy Flex Installer Manual
Parameters [51]
95
To select a preset, enter an option number from the tables below:
Option
Double balanced
End of line
Split resistance
01
1k
-
-
02
-
1k
-
03
2k2
-
-
04
-
2k2
-
05
4k7
-
-
06
-
4k7
-
07
5k6
-
-
08
-
5k6
-
09
3k3
-
-
10
-
3k3
-
11
1k fault
-
-
12
-
1k fault
-
13
1k N/O
-
-
14
-
0k N/C
-
15
-
-
2k2, 4k7
16
2k
-
-
Table 2 Resistance values
The operating range for each resistance value is shown in
Appendix H: Resistance tables
on
page 255.
When a preset is selected it sets the zone resistance range used by every zone on the system.
Each zone on the system can be further customised to a specific preset by using the
Resistance Select [52.9]
option.
Set Confirm [51.47]
Use this option to cause the system to emit a short double beep when the system/group has
set. There are three options:
0=Off
No indication.
1=Alert on Set
A double beep when the system has set.
2=Alert on Comm
A double beep after a successful signal to the ARC that setting has
occurred.
Alarm Limits [51.48]
Use this parameter to program the maximum number of alarms, per group, which may be
transmitted to an Alarm Receiving Centre in any set period. There are three options: