Galaxy Flex Installer Manual
Wire detectors to zones
17
Wire detectors to zones
Note:
Learning wireless detectors is covered on page 27.
Zones are the individual input circuits that are fully programmable using the
Zones
menu
(
52 ent
). This section describes how to change zone default settings, how to terminate
unused zones, and how to connect detectors.
Zone addressing
The zone address format is:
The RIO address range is 00 to 12, and each RIO can support up to 8 zones. Camera zones
use these addresses in order of connection: 8001, 8011, 8021, 8031 and 8041.
Note:
RIO 100 and 101 are the fixed on-board RIO addresses.
Address on-board zones as follows:
Zone
Address
Zone
Address
1
1001 (Final)
7
1013 (Intruder)
2
1002 (Exit)
8
1014 (Intruder)
3
1003 (Intruder)
9
1015 (Intruder)
4
1004 (Intruder)
10
1016 (Intruder)
5
1011 (Intruder)
11
1017 (Intruder)
6
1012 (Intruder)
12
1018 (Intruder)
If required, use the Descriptor menu (
52 ent 2 ent
) to name your zones.
Zone configuration
Note:
The circuit debounce time (the period the zone must remain in a state to register a
change in condition) is 300 ms.
The default zone configuration is 1 k
Ω
double-balanced with fault monitoring via a 3 k
Ω
resistor (preset 11). In the following configuration a mask condition is generated if an alarm
and fault are signalled at the same time.