Galaxy Flex Installer Manual
View zone information
33
Section 2: Commissioning and
handover
View zone information
Display zones (
21 ent
). View information about any selected zone.
Walk test
1.
Select Test All Zones (
31 ent 2 ent 2 ent 1
) to perform an audible test. Alternatively,
to perform a silent test, press
31 ent 2 ent 1 ent 1
.
It is possible to walk test selected zones only. Refer to
Walk Test [31]
.
2.
Activate each zone in turn.
Note:
If you do not activate any zone for 20 minutes the test will stop automatically.
3.
To end the test, press
esc
.
Walk test results
To view the results of your walk test, select Display Log (
22 ent
).
Test outputs
Outputs are tested by function, for example Bells or Strobe.
1.
Select Outputs (
32 ent
).
01=Bells
is displayed on the keypad.
2.
Press
A
or
B
to move to the output you wish to test, or type its number.
3.
Press
ent
to test the selected output device.
4.
Press
ent
to stop the test.
5.
Repeat steps 2 to 4 to select and test other outputs.
6.
Press
esc
to exit the Test Output function.
Diagnostic test (optional)
Check the Latest (
61 ent 1 ent
) and Historical (
61 ent 2 ent
) status of:
Modules
PSU
baseline record